BATCH interface blocks
2.2 IEOP
The block allows the following status changes:
Operating principle
● Allocate / Enable
● Control commands
22
A recipe step can occupy the block by setting the identifier OCCUPIED = 1. It also enters
an occupied information based on the batch name, batch number, the step number
(UBA_NAME, UBA_ID, USTEP_NO) and, if necessary, the step monitoring time
(STEP_T). The block is only occupied if enabled for BATCH (BA_EN = 1), if set to auto
mode (status word bit 17 = 1), and if there is no active group error (status word bit
31 = 0).
The block is controlled by way of the ISTART, IHOLD, IABORT, ISTOP, ITERM, IRESET
(for interconnection in CFC) control inputs, or by means of control word ICTRL (used only
in BATCH). The active control commands can be read from the corresponding outputs,
for example QSTART. Control word ICTRL enables the consistent writing of control
commands in BATCH. Example: ICTRL = 1 ensures that ISTART = 1 and IHOLD = 0 are
written simultaneously. The control inputs are reset automatically after the corresponding
end status was reached (reset of ISTART at the positive of the RUNNING bit in
USTAT_L, for example).
SIMATIC BATCH Interface Blocks V7.1
Function Manual, 03/2009, A5E02171101-01