Guide Specifications (Cont'd)
JOHNSON CONTROLS
(Optional) A harmonic filter that limits electrical power supply distortion from the variable
speed drive in order to help the building comply with the guidelines of IEEE STD. 519-
2014 shall be provided. The filter shall be unit mounted within the same NEMA 1 enclo-
sure and shall be UL listed. The following digital readouts shall be provided at the chiller
unit control panel as part of the filter package:
• Input KVA
• Total power-factor
• 3-phase input voltage
• 3-phase input current
• 3-phase input voltage total harmonic distortion (THD)
• 3-phase input current total demand distortion (TDD)
• Self diagnostic service parameters
Separate meters for this information shall not be acceptable.
FACTORY-INSTALLED COMPRESSOR MOTOR STARTER [OPTION THROUGH 900
HP (671 KW) 200 600 VOLTS]
The chiller manufacturer shall furnish a reduced voltage Solid-State Starter for the com-
pressor motor. Starter shall be factory mounted and wired on the chiller. The starter shall
provide, through the use of silicon-controlled rectifiers, a smooth acceleration of the motor
without current transitions or transients. The starter enclosure shall be NEMA 1, with a
hinged access door with lock and key. Electrical lugs for incoming power wiring shall be
provided.
Standard Features include: digital readout at the OptiView™ Control Center of the follow-
ing:
Display Only
• 3-phase voltage A, B, C
• 3-phase current A, B, C
• Input Power (kW)
• kW Hours
• Starter Model
• Motor Run (LED)
• Motor Current % Full Load Amps
• Current Limit Setpoints
• Pulldown Demand Time Left
FORM 160.75-EG1 (519)