Motor Electrical Data; Motor Voltage Variations - York YK Manual

Centrifugal liquid chiller style g
Hide thumbs Also See for YK:
Table of Contents

Advertisement

Application Data (Cont'd)
JOHNSON CONTROLS
TABLE 5 - MOTOR VOLTAGE VARIATIONS
RATED
FREQ.
VOLTAGE
60 HZ
2300
3300
4000
50 HZ
3300
*For motor voltage above 4160V/60Hz and 3300V/50HZ, contact your JCI Sales Office for a specific selection.

MOTOR ELECTRICAL DATA

The smallest motor available which equals or exceeds the Input power (kW) from the
chiller rating program is selected from Table 9 on page 60 to Table 12 on page 62.
The full load amperes (FLA) listed in the tables is maximum values and corresponds to
the maximum motor kW listed. When the input power (kW) is less than maximum motor
kW, the FLA should be reduced per the following equation:
FLA =
The benefit from the FLA correction is the possible use of smaller power wiring and/or
starter size. The locked rotor amperes (LRA) are read directly from Table 9 to Table 12 for
specific Motor Code and voltage.
This is because the LRA is dependent only on motor size and voltage and is independent
of input power (kW). Inrush amperes (IRA) depend on LRA and the type of starter applied.
The inrush can be calculated using a percentage of LRA shown in Table 9 to Table 12.
NAMEPLATE
VOLTAGE*
200
200/208
230
220/240
380
380
416
416
460
440/460/480
575
575/600
2300
3300
4000/4160
346
346
380
380/400
415
415
3300
Motor kW x
Maximum Motor FLA
Maximum Motor kW
FORM 160.75-EG1 (519)
OPERATING VOLTAGE
MIN.
MAXIMUM
180
220
208
254
342
415
375
457
414
508
520
635
2070
2530
2970
3630
3600
4576
311
381
342
423
374
440
2970
3630
47