Application Data (Cont'd)
TABLE 7 - HYBRID FALLING FILM EVAPORATOR WATER FLOW RATE LIMITS GPM (L/S) – BASED UPON
STANDARD TUBES @ DESIGN FULL LOAD CONDITIONS (CONT'D)
1 PASS
MODEL
MIN
3199
QD
(202)
3680
QF
(232)
1902
QH
(120)
2580
Q5
(163)
3027
Q7
(191)
JOHNSON CONTROLS
HYBRID FALLING FILM EVAPORATORS
2 PASS
MAX
MIN
12794
1598
(807)
(101)
14722
1839
(929)
(116)
7608
951
(480)
(60)
10319
1287
(651)
(81)
12107
1510
(764)
(95)
3 PASS
MAX
MIN
MAX
4526
1065
3042
(286)
(67)
(192)
5268
1227
3479
(332)
(77)
(220)
2799
(177)
4734
(299)
3716
5456
1009
(344)
(64)
(234)
FORM 160.75-EG1 (519)