X302 Power Supply 2 Terminal Block; X305 Jumper - Power Supply 2 On/Off - Siemens FCI2016-U1 Mounting & Installation

Periphery board (250p) / periphery board (500p)
Table of Contents

Advertisement

Periphery board (250p) FCI2016
1
Configuration input power and battery

1.4.3 X302 Power supply 2 terminal block

1.4.4 X305 jumper – Power supply 2 on/off
X305
Jumper position
1 - 2
3
2
1
2 - 3
3
2
1
12 | 46
Building Technologies
Siemens Industry, Inc.
Terminal block X302 may only be used for an additional PS300 when the system
requirements exceed 300 W. The housing (3HU) is the only housing that is capable of
having two PS300 supplies connected at the same time. No power supply (170 W)
may be connected to terminal block X302.
Terminal X301 must always have a power supply connected. When a single power
supply is used, it must be connected to terminal X301.
Check whether jumper X305 is in position 2-3 before PS300 #1 is connected to X301
or #2 to X302. Make sure line voltage is not present on the system, and that the
breaker in the panel is off. Both power supplies need to be connected before line
voltage is switched on at the panel. X301 and X302 should never be
connected/disconnect with line voltage present. Batteries may only be connected after
the system is brought up on line voltage power.
Pin
Designation
1
BROO
2
PSSI
3
GND
4
+24 V
Admissible cable cross-section: 1 x 12...18 AWG or 2 x 16...18 AWG
This jumper is used to configure the periphery board for one or two power supplies.
The factory setting may only be changed when a second power supply (300 W) in an
housing (3HU) is supported.
Function
Meaning
Deactivated
Default setting; for power supply (170 W) and a single power
PS 2 300 W
supply (300 W).
For a second power supply (300 W) in an housing (3HU).
Activated
PS 2 300 W
The power supply is activated and is monitored by the system.
Description
(White) AC low signal. Signals when the supply system
connection drops below AC 102 V.
(Green) Power supply status indication. Used by the
periphery board to know the health of the power supply.
(Black) Return (ground)
(Red) DC +24 V system supply
A6V10315038_f_en_--