Periphery board (500p) FCI2017
2
Technical data
2.12 Technical data
Supply input
Battery
NAC circuit
AUX output
42 | 46
Building Technologies
Siemens Industry, Inc.
Plug strip
Operating voltage
Operating current (standby)
Max. operating current.
Input current (active)
Design
Plug strip
Voltage
Curent
Plug strip
Voltage
Standby operating current
Active operating current
Maximum circuit resistance
Supervised for
Design
Plug strip
Voltage
Curent
Design
X301/302
DC 24 V nominal, filtered
120 mA
136 mA
●
PS170W (only fire detection
systems) 6.5 A at
●
1 x PS300W 11.5 A
●
2 x PS300W 20 A
Not power limited
X303
DC 20.4 V...DC 26.4 V
(DC 24 V nominal)
11.5 A
X601
DC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Max. 10 mA
Max. 1x class A circuit or 2x class B
circuits
Max. 3 A for 1x class A circuit
Max. 3 A per class B circuit
2x 3 A = 6 A for 2x class B circuits
1.4 Ω @ 3.0 A
●
Open circuit
●
Short circuit
●
Ground fault
●
Short-circuit protection
●
Voltage surge protection
●
Power limited
X1001
DC 24 V nominal "Special Application"
For use with: FN2006/FN2007, HZM,
HCP, FCA2018, FT2014/FT2015,
FTI2001
Max. 1.5 A
●
Short-circuit protection
●
Voltage surge protection
●
Power limited
A6V10315038_f_en_--