Technical Data - Siemens FCI2016-U1 Mounting & Installation

Periphery board (250p) / periphery board (500p)
Table of Contents

Advertisement

Periphery board (500p) FCI2017
2

Technical data

2.12 Technical data
Supply input
Battery
NAC circuit
AUX output
42 | 46
Building Technologies
Siemens Industry, Inc.
Plug strip
Operating voltage
Operating current (standby)
Max. operating current.
Input current (active)
Design
Plug strip
Voltage
Curent
Plug strip
Voltage
Standby operating current
Active operating current
Maximum circuit resistance
Supervised for
Design
Plug strip
Voltage
Curent
Design
X301/302
DC 24 V nominal, filtered
120 mA
136 mA
PS170W (only fire detection
systems) 6.5 A at
1 x PS300W 11.5 A
2 x PS300W 20 A
Not power limited
X303
DC 20.4 V...DC 26.4 V
(DC 24 V nominal)
11.5 A
X601
DC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Max. 10 mA
Max. 1x class A circuit or 2x class B
circuits
Max. 3 A for 1x class A circuit
Max. 3 A per class B circuit
2x 3 A = 6 A for 2x class B circuits
1.4 Ω @ 3.0 A
Open circuit
Short circuit
Ground fault
Short-circuit protection
Voltage surge protection
Power limited
X1001
DC 24 V nominal "Special Application"
For use with: FN2006/FN2007, HZM,
HCP, FCA2018, FT2014/FT2015,
FTI2001
Max. 1.5 A
Short-circuit protection
Voltage surge protection
Power limited
A6V10315038_f_en_--
2016-02-25