1.7 Auxiliary DC 24 V output

1.7.1 Wiring

1.7.2 X1001 Auxiliary output terminal block

1.8 Relays

Building Technologies
Siemens Industry, Inc.
Auxiliary output DC 24 V with a maximum output current of 1.5 A. The output can be
used for devices such as door holders, DACT, or RDT. The circuit is power limited and
is protected against a direct shorted output. The output is power limited and supervised
for overcurrent. To configure the output to shut down during AC loss to conserve the
battery, you must configure the system with the Engineering tool set.
If the output is configured to turn off on battery, then the output is used for
supplementary purposes only.
X1001
AUX
AUX
AUX
AUX
Pin
Designation
1
AUX (+)
2
AUX (-)
3
AUX (+)
4
AUX (-)
Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 AWG
Common alarm relay
The alarm relay changes state whenever a fire alarm is detected. In degrade mode, the
alarm relay will still activate in case of a fire, without processor control.
Common trouble relay
The trouble relay changes state whenever a system trouble is detected. In degrade
mode, the trouble relay will still activate without processor control.
Common supervisory relay
The supervisory relay changes state whenever a supervisory trouble is detected. In
degrade mode, the supervisory relay will not function.
Programmable user relay
The user programmable relay changes state depending on the configuration set in the
Engineering tool set.
In degrade mode, the user relay will not activate.
Periphery board (250p) FCI2016
+
1
-
2
+
3
-
4
Description
Positive feed for Aux circuit (DC +24 V)
Return feed Aux circuit
Positive feed for Aux circuit (DC +24 V)
Return feed Aux circuit
Auxiliary DC 24 V output