Wiring The Nac Circuits - Siemens FCI2016-U1 Mounting & Installation

Periphery board (250p) / periphery board (500p)
Table of Contents

Advertisement

Periphery board (500p) FCI2017
2
NAC circuits

2.5.1 Wiring the NAC circuits

2.5.2 X601 terminal block – NAC 1 class A / NAC 1-1 class B / NAC
Pin
Designation
4
NAC1-1 (+)
3
NAC1-1 (-)
2
NAC1-2 (+)
1
NAC1-2 (-)
34 | 46
Building Technologies
Siemens Industry, Inc.
The following wiring diagrams show how to connect notification devices to the circuit,
either as class A (style Z) or class B (style Y) circuit. For class A, no end-of-line resistor
is needed. It is built into the circuit.
To ensure proper functioning, the jumpers must be set correctly for class A/B
selection.
In the diagrams below, polarity is shown in activated condition.
Notification appliance circuit supervised and power limited.
X601
+
NAC1-1
-
NAC1-1
+
NAC1-2
-
NAC1-2
Figure 9: X601: Class A (style Z) supervised output connection
X601
+
NAC1-1
-
NAC1-1
+
NAC1-2
-
NAC1-2
Figure 10: X601: Class B (style Y) supervised output connection
* EOL resistance must be connected during non-use.
EOL resistance: 2.4 kΩ, 0.5 W
1-2 class B
Description
Positive feed for notification appliances for NAC 1 class A or NAC 1-1 class B
Return feed for notification appliances for NAC 1 class A or NAC 1-1 class B
Positive feed for notification appliances for NAC 1 class A or NAC 1-2 class B
Return feed for notification appliances for NAC 1 class A or NAC 1-2 class B
Admissible cable cross-section: 1 x 12...18 AWG or 2 x 16...18 AWG
+
4
-
3
2
1
+
4
-
3
*
2
EOL
1
+
-
+
EOL
-
A6V10315038_f_en_--
2016-02-25