Ccn Display Tables - Carrier AquaSnap 30MPA Series Controls, Start-Up, Operation, Service, And Troubleshooting

Liquid chillers with scroll compressors and comfortlink controls
Hide thumbs Also See for AquaSnap 30MPA Series:
Table of Contents

Advertisement

TABLE
DISPLAY NAME
A-UNIT
GENERAL UNIT PARAMETERS
Control Mode
Occupied
CCN Chiller
Alarm State
Active Demand Limit
Override Modes in Effect
Percent Total Capacity
Requested Stage
Active Setpoint
Control Point
Degrees of Reset
Entering Fluid Temp
Leaving Fluid Temp
Emergency Stop
Minutes Left for Start
PUMPS
Cooler Pump Relay
Condenser Pump
Cooler Flow Switch
Condenser Flow Switch
CIRCA_AN
CIRCUIT A ANALOG
PARAMETERS
Percent Total Capacity
Percent Available Cap.
Discharge Pressure
Suction Pressure
Head Setpoint
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
CIRCADIO
CIRCUIT A DISCRETE INPUTS/
OUTPUTS
CIRC. A DISCRETE OUTPUTS
Compressor A1 Relay
Compressor A1 Unload Time
Compressor A2 Relay
Compressor A3 Relay
Minimum Load Valve Relay
CIRC. A DISCRETE INPUTS
Compressor A1 Feedback
Compressor A2 Feedback
Compressor A3 Feedback
OPTIONS
UNIT PARAMETERS
UNIT ANALOG VALUES
Cooler Entering Fluid
Cooler Leaving Fluid
Condenser Entering Fluid
Condenser Leaving Fluid
Lead/Lag Leaving Fluid
TEMPERATURE RESET
4-20 ma Reset Signal
Outside Air Temperature
Space Temperature
DEMAND LIMIT
4-20 ma Demand Signal
Demand Limit Switch 1
Demand Limit Switch 2
CCN Loadshed Signal
MISCELLANEOUS
Dual Setpoint Switch
Cooler LWT Setpoint
Ice Done
APPENDIX B — CCN TABLES

CCN DISPLAY TABLES

RANGE
UNITS
10-char ASCII
No/Yes
Stop/Start
6-char ASCII
NNN
%
No/Yes
NNN
%
NN
NNN.n
degF
NNN.n
degF
NN.n
deltaF
NNN.n
degF
NNN.n
degF
Enable/EMStop
5-char ASCII
Off/On
Off/On
Off/On
Off/On
NNN
%
NNN
%
NNN.n
PSIG
NNN.n
PSIG
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
deltaF
Off/On
NN
secs
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NN.n
milliAmps
NNN.n
degF
NNN.n
degF
NN.n
milliAmps
Off/On
Off/On
N
Off/On
NNN.n
degF
Off/On
82
POINT NAME
WRITE STATUS
STAT
OCC
CHIL_S_S
forcible
ALM
DEM_LIM
forcible
MODE
CAP_T
STAGE
SP
CTRL_PNT
forcible
DEG_RST
EWT
LWT
EMSTOP
forcible
MIN_LEFT
COOLPUMP
CONDPUMP
COOLFLOW
CONDFLOW
CAPA_T
CAPA_A
DP_A
SP_A
HSP
TMP_SCTA
TMP_SSTA
TMP_RGTA
DISGAS
SH_A
K_A1_RLY
ALUNLTME
K_A2_RLY
K_A3_RLY
MLV_RLY
K_A1_FBK
K_A2_FBK
K_A3_FBK
COOL_EWT
COOL_LWT
COND_EWT
COND_LWT
DUAL_LWT
RST_MA
OAT
forcible
SPT
forcible
LMT_MA
DMD_SW1
DMD_SW2
DL_STAT
DUAL_IN
LWT_SP
ICE_DONE