Ccn Configuration Tables - Carrier AquaSnap 30MPA Series Controls, Start-Up, Operation, Service, And Troubleshooting

Liquid chillers with scroll compressors and comfortlink controls
Hide thumbs Also See for AquaSnap 30MPA Series:
Table of Contents

Advertisement

TABLE
DISPLAY NAME
RUNTEST
Percent Total Capacity
Percent Available Cap.
Discharge Pressure
Suction Pressure
Saturated Condensing Tmp
Saturated Suction Temp
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
Compressor A1 Relay
Compressor A2 Relay
Compressor A3 Relay
Minimum Load Valve Relay
Compressor A1 Feedback
Compressor A2 Feedback
Compressor A3 Feedback
Outside Air Temperature
Space Temperature
Cooler Pump Relay
Condenser Pump
Cooler Entering Fluid
Cooler Leaving Fluid
Condenser Entering Fluid
Condenser Leaving Fluid
Cooler Flow Switch
DUALCHIL
Dual Chiller Link Good?
Master Chiller Role
Slave Chiller Role
Lead Chiller Ctrl Point
Lag Chiller Ctrl Point
Control Point
Cool EnteringFluid-Slave
Cool Leaving Fluid-Slave
Cooler Entering Fluid
Cooler Leaving Fluid
Lead/Lag Leaving Fluid
Percent Avail.Capacity
Percent Avail.Cap.Slave
Lag Start Delay Time
Load/Unload Factor
Load/Unload Factor-Slave
Lead SMZ Clear Commanded
Lag SMZ Clear Commanded
Lag Commanded Off?
Dual Chill Lead CapLimit
Dual Chill Lag CapLimit
TABLE
DISPLAY NAME
UNIT
UNIT CONFIGURATION
Unit Type
Unit Size
Compressor A1 Size
Compressor A2 Size
Compressor A3 Size
Suction Superheat Setpt
Compressor A1 Digital?
Maximum A1 Unload Time
OPTIONS1
OPTIONS 1 CONFIGURATION
Cooler Fluid
Minimum Load Vlv Select
Return Gas Sensor Enable
Enable OAT Sensor
CSB Boards Enable
Reverse Rotation Enable
Cooler Pump Control
Cooler Pump Shutdown Dly
EMM Module Installed
Enable Condenser Pump
Enable Cond Wtr Sensors
Enable Cond Flow Switch
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES (cont)
RANGE
NNN
%
NNN
%
NNN.n
PSIG
NNN.n
PSIG
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
deltaF
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
NNN.n
degF
NNN.n
degF
Off/On
Off/On
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
Off/On
No/Yes
12-char ASCII
12-char ASCII
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN.n
degF
NNN
%
NNN
%
5-char ASCII
NNN
NNNN
No/Yes
No/Yes
No/Yes
NNN.n
%
NNN.n
%

CCN CONFIGURATION TABLES

RANGE
N
NNN
tons
NNN
tons
NNN
tons
NNN
tons
NN.n
deltaF
No/Yes
NN
secs
N
1=Water
2=Medium Temperature
Brine
No/Yes
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Off/On
NN
mins
No/Yes
N
0=No Control
1=On When Occupied
2=On with Compressors
Disable/Enable
Disable/Enable
85
UNITS
POINT NAME
CAPA_T
CAPA_A
DP_A
SP_A
TMP_SCTA
TMP_SSTA
TMP_RGTA
DISGAS
SH_A
K_A1_RLY
K_A2_RLY
K_A3_RLY
MLV_RLY
K_A1_FBK
K_A2_FBK
K_A3_FBK
OAT
SPT
COOLPUMP
CONDPUMP
COOL_EWT
COOL_LWT
COND_EWT
COND_LWT
COOLFLOW
DC_LINK
MC_ROLE
SC_ROLE
LEAD_CP
LAG_CP
CTRL_PNT
COOLEWTS
COOLLWTS
COOL_EWT
COOL_LWT
DUAL_LWT
CAP_A
CAP_A_S
LAGDELAY
SMZ
SMZSLAVE
LEADSMZC
LAG_SMZC
LAG_OFF
DCLDCAPL
DCLGCAPL
UNITS
POINT NAME
UNIT_TYP
SIZE
SIZE_A1
SIZE_A2
SIZE_A3
SH_SP
CPA1TYPE
MAXULTME
FLUIDTYP
MLV_FLG
RGT_ENA
OAT_ENA
CSB_ENA
REVR_ENA
CPC
PUMP_DLY
EMM_BRD
CONDPMPE
CONDWTRS
CONDFLSW
WRITE STATUS
DEFAULT
Unit Dependent
Unit Size
Unit Size Dependent
Unit Size Dependent
Unit Size Dependent
9.0 deg F
Unit Dependent
10 - 020 to 030
7 - 035 to 045
1=Water
No
Disable
Disable
Enable
Enable
Off
1
No
0=No Conrol
Disable
Disable

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquasnap 30mpa015Aquasnap 30mpw071Aquasnap 30mpa071Aquasnap 30mpw015Aquasnap 30mpw seriesAquasnap 30mpa,mpw020 ... Show all

Table of Contents