MODE
KEYPAD
(RED LED)
ENTRY
ENTER
CONFIGURATION
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 19 — Outdoor-Air Temperature Reset
LEGEND
LWT — Leaving Water (Fluid) Temperature
Fig. 20 — Space Temperature Reset
Table 30 — Configuring Return Temperature Reset
SUB-MODE KEYPAD
ITEM
ENTRY
DISP
TEST
ENTER
UNIT
TYPE
ENTER
OPT1
FLUD
ENTER
OPT2
CTRL
ENTER
CCN
EXV.A
RSET
CRST
ENTER
RT.NO
RT.F
RT.DG
ITEM
DISPLAY
EXPANSION
ON/OFF
TEST DISPLAY LEDs
X
UNIT TYPE
X
COOLER FLUID
X
CONTROL METHOD
3
COOLING RESET TYPE
RETURN FLUID - NO
10.0 F
RESET TEMP
RETURN FLUID - FULL
2.0 F
RESET TEMP
RETURN - DEGREES
5.0 F
RESET
54
12.2
11.1
54
50
10.0
48
8.9
46
7.8
44
6.7
SET POINT — 44 F
DESIGN RISE — 10 F
42
5.6
0
10
LEGEND
Entering Water (Fluid) Temperature
EWT
Leaving Water (Fluid) Temperature
LWT
Fig. 21 — Standard Chilled Fluid
Temperature Control — No Reset
10
9
8
7
6
RT.F = 2
5
4
3
CHANGE IN
LIMIT SETPOINT
2
1
0
0
1
2
ΔT (°F or °C), Entering Fluid Temperature - Leaving Fluid Temperature
Fig. 22 — Return Fluid Reset
33
COMMENT
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM TB6-2,3)
2 = Outdoor-Air Temperature
3 = Return Fluid
4 = Space Temperature
(Connect to TB5-5,6)
Default: 10.0 F (5.6 C)
Range: 0° to 30 F COOLER DT
(0.0 to 16.7 C)
Default: 0 F (–17.8 C)
Range: 0° to 30 F COOLER DT
(0.0 to 16.7 C)
Default: 0 F (0 C)
Range: –30 to 30°F (–16.7 to 16.7 C)
DESIGN RISE
LWT
20
30
40
50
60
70
% UNIT LOADING
DESIGN RISE
CHANGE IN CHILLED
ΔT
FLUID,
RESET AMOUNT
RT.NO = 10
3
4
5
6
7
8
80
90
100
RT.DG = 5
9