Configuration Mode And Sub-Mode Directory - Carrier AquaSnap 30MPA Series Controls, Start-Up, Operation, Service, And Troubleshooting

Liquid chillers with scroll compressors and comfortlink controls
Hide thumbs Also See for AquaSnap 30MPA Series:
Table of Contents

Advertisement

ITEM
CIR.A
OUTPUTS CIRCUIT A
CC.A1
Compressor A1 Relay
D.PER
Compressor A1 Load Percent
CC.A2
Compressor A2 Relay
CC.A3
Compressor A3 Relay
CCH
Crankcase Heater Relay
LLSV
Liquid Line Solenoid
MLV.R
Minimum Load Valve Relay
A.EXV
EXV.A
EXV% Open
APPR
Circuit A Approach
AP.SP
Approach Setpoint
X.SH.R
SH Reset at Max Unl-Dig
S.SH.R
Digload to Start SH RST
SH_R
Amount of SH Reset
OVR.A
EXVA Override
SPH.A
Suction Superheat Temp
ASH.S
Active Superheat Setpt
AMP.S
Active Mop Setpt
PLM.A
Cir A EXV Position Limit
ITEM
EXPANSION
DISP
DISPLAY CONFIGURATION
TEST
Test Display LEDs
METR
Metric Display
LANG
Language Selection
PAS.E
Password Enable
PASS
Service Password
UNIT
UNIT CONFIGURATION
TYPE
Unit Type
SIZE
Unit Size
SZA.1
Compressor A1 Size
SZA.2
Compressor A2 Size
SZA.3
Compressor A3 Size
A1.TY
Compressor A1 Digital?
MAX.T
Maximum A1 Unload Time
D.TYP
Discharge Gas Therm Type
OPT1
UNIT OPTIONS 1 HARDWARE
FLUD
Cooler Fluid
MLV.S
Minimum Load Vlv Select
RG.EN
Return Gas Sensor Enable
OAT.E
Enable OAT Sensor
CSB.E
CSB Boards Enable
CPC
Cooler Pump Control
PM.DY
Cooler Pump Shutdown Dly
D.PM.E
Enable Condenser Pump
D.FL.S
Enable Cond Flow Switch
CDWS
Enable Cond Wtr Sensors
OPT2
UNIT OPTIONS 2 CONTROLS
CTRL
Control Method
LCWT
High LCW Alert Limit
DELY
Minutes Off Time
ICE.M
Ice Mode Enable
APPENDIX A — LOCAL DISPLAY TABLES (cont)
Outputs Mode and Sub-Mode Directory (cont)
EXPANSION
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON

Configuration Mode and Sub-Mode Directory

RANGE
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
DSBL/ENBL
0 to 9999
2=Air Cooled,
3=Water Cooled
15 to 74
Unit Size Depen-
dent
Unit Size Depen-
dent
Unit Size Depen-
dent
0 to 15
0 = 86K
1 = 100K
1 = Water
2 = Medium Temp
Brine
0 to 10
0=No Control
1=On When Occu-
pied
2=On with Com-
pressors
0=Switch
1=Occupancy
2=Occupancy
3=CCN
2 to 60°F
0 to 15
UNITS
CCN POINT
K_A1_RLY
DIGITALP
K_A2_RLY
K_A3_RLY
CCH_RLY
LLSV_A
MLV_RLY
EXV_A
CIRA_APP
APPRA_SP
MAXSHRST
SHRSTBGN
SH_RESET
EXVAOVRR
SH_A
ACTSH_SP
ACMOP_SP
PLMA
UNITS
OFF/ON
DISPTEST
OFF = English
DISPUNIT
ON = Metric
X
LANGUAGE
PASS_EBL
XXXX
PASSCOPY
X
UNIT_TYP
XXX
SIZE
XX
SIZE_A1
XX
SIZE_A2
XX
SIZE_A3
NO/YES
CPA1TYPE
XX
MAXULTME
X
DGASTYPE
X
FLUIDTYP
NO/YES
MLV_FLG
DSBL/ENBL
RGT_ENA
DSBL/ENBL
OAT_ENA
DSBL/ENBL
CSB_ENA
OFF/ON
CPC
XX MIN
PUMP_DLY
X
CONDPMPE
DSBL/ENBL
CONDFLSW
DSBL/ENBL
CONDWTRS
X
CONTROL
XX
LCW_LMT
XX
DELAY
DSBL/ENBL
ICE_CNFG
(Requires EMM)
75
COMMENT
CCN POINT
DEFAULT
OFF = English
0
ENBL
1111
7 (040,045)
10 (020,030)
0
1 = Water
NO
ON
1 MIN
0=No Control
DSBL
DSBL
0=Switch
60°F
0
DSBL