ITEM
VIEW
AUTO VIEW OF RUN STATUS
EWT
Entering Fluid Temp
LWT
Leaving Fluid Temp
SETP
Active Setpoint
CTPT
Control Point
LOD.F
Load/Unload Factor
STAT
Control Mode
OCC
Occupied
MODE
Override Modes in Effect
CAP
Percent Total Capacity
DEM.L
Active Demand Limit
STGE
Requested Stage
ALRM
Current Alarms and Alerts
TIME
Time of Day
MNTH
Month of Year
DATE
Day of Month
YEAR
Year of Century
RUN
UNIT RUN HOUR AND START
HRS.U
Machine Operating Hours
STR.U
Machine Starts
HR.P1
Cooler Pump Run Hours
HR.P2
Condenser Pump Run Hours
HOUR
CIRC AND COMP RUN HOURS
HR.A1
Compressor A1 Run Hours
HR.A2
Compressor A2 Run Hours
HR.A3
Compressor A3 Run Hours
STRT
COMPRESSOR STARTS
ST.A1
Compressor A1 Starts
ST.A2
Compressor A2 Starts
ST.A3
Compressor A3 Starts
PM
PREVENTIVE MAINTENANCE
STRN
STRAINER MAINTENANCE
STRN
SI.ST
Strainer Srvc Interval
STRN
S.T.DN
Strainer Srvc Countdown
STRN
S.T.MN
Strainer Maint. Done
ST.DT
STRAINER MAINT. DATES
ST.DT
S.T.M0
ST.DT
S.T.M1
ST.DT
S.T.M2
ST.DT
S.T.M3
ST.DT
S.T.M4
VERS
SOFTWARE VERSION NUMBERS
MBB
CESR131482-xx-xx
EXV*
CESR131172-xx-xx
AUX1*
CESR131333-xx-xx
EMM*
CESR131174-xx-xx
MARQ
CESR131171-xx-xx
NAVI*
CESR130227-xx-xx
* If these devices are not installed, they will not show in the table.
APPENDIX A — LOCAL DISPLAY TABLES

Run Status Mode and Sub-Mode Directory

EXPANSION
0=Service Test
1=Off Local
2=Off CCN
3=Off Time
4=Off Emergency
5=On Local
6=On CCN
7=On Time
9=Pump Delay
00:00 to 23:59
1 to 12
(1 = January,
2 = February, etc.)
01 to 31
0 to 999999
0 to 1000000
0 to 999999.9
0 to 999999.9
0 to 999999
0 to 999999
0 to 999999
0 to 999999
0 to 999999
0 to 999999
0 to 65535
0 to 65535
RANGE
UNITS
xxx.x °F
xxx.x °F
xxx.x °F
xxx.x °F
xxx
x
NO/YES
NO/YES
xxx
x
xxx
xx.xx
xx
xx
xx
xxxx HRS
xxxx
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx HRS
xxxx
xxxx
xxxx
xxxx HRS
xxxx HRS
NO/YES
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
MM/DD/YY HH:MM
72
CCN POINT
COMMENT
EWT
LWT
SP
CTRL_PNT
SMZ
STAT
OCC
MODE
CAP_T
DEM_LIM
STAGE
ALRMALRT
TIMECOPY
MOY
DOM
YOCDISP
HR_MACH
CY_MACH
HR_CPUMP
HR_DPUMP
HOURS_A1
HOURS_A2
HOURS_A3
CY_A1
CY_A2
CY_A3
SI_STRNR
ST_CDOWN
Default: 8760
ST_MAINT