Parameter List - Samson TROVIS 5724-3 Mounting And Operating Instructions

Electric actuators with process controllers for domestic hot water heating. with/without fail-safe action
Hide thumbs Also See for TROVIS 5724-3:
Table of Contents

Advertisement

10.3 Parameter list

The parameters have the setting ranges as listed below.
P = Parameter
P
Parameters
01
Set point W1
02
Set point W2
03
Lower measuring range value Xmin
04
Upper measuring range value Xmax
05
Upper limit (GWH)
06
Lower limit (GWL)
07
Proportional-action coefficient KP
08
Reset time Tn
09
Derivative-action time Tv
10
Actuator transit time Ty
11
Set-back difference
12
Heating period to maintain heat exchanger at
constant temperature
EB 5724 EN
WE = Default setting
WE
Adjustment range
60 °C
0 to 100 °C
70 °C
0 to 100 °C
0 °C
–50 to 90 °C
100 °C
10 to 150 °C
95 °C
0 to 100 °C
5 °C
0 to 20 °C
0.6
0.1 to 50
25 s
0 to 999 s
0 s
0 to 999 s
35 s
0 to 240 s
8 K
0 to 30 K
24 h
0.0 to 25.5 h
Appendix