The table below describes the various event classes and numbers.
Table 8- 1
Event classes and event numbers
Event class 0 (00H):
"CP start-up"
Event no.
Event text
(00)03H
PtP parameters received
(00)04H
Parameters already on CP (time versions match)
(00)07H
Status transition CPU to STOP
(00)08H
Status transition CPU to RUN/STARTUP
Event Class 1 (01H):
"Hardware fault on CP"
Event no.
Event text
(01)01H
Fault while testing operating system EPROM of CP
(01)02H
RAM test of CP errored
(01)03H
Request interface of CP defective
(01)10H
Fault in CP firmware
Event Class 2 (02H):
"Initialization error"
Event no.
Event text
(02)0FH
Invalid parameter assignment detected at start of
assigned communication. Interface parameters
could not be assigned.
Event class 3(03H):
"Error during parameter assignment of FBs" (not displayed in the diagnostic buffer)
Event no.
Event text
(03)01H
Illegal or missing source/destination data type Area
(start address, length) not permitted
The DB is not permitted or does not exist (e.g.,
DB 0) or
Other data type invalid or missing
Interprocessor communication byte number invalid
or
Interprocessor communication bit number invalid or
neither 'S' nor 'F' selected (for FB P_SND_RK)
188
www.gkbpx.com
Remedy
-
-
-
-
Remedy
CP defective; replace CP.
Switch module off and on again. If necessary,
replace module.
Remedy
Correct invalid parameters and restart.
Remedy
Check parameter assignment on CPU and CP, and
correct if necessary.
RK 512 only: Partner returns invalid parameters in
message frame header.
Check parameter assignment on CPU and CP;
create block, if necessary.
See request tables for valid data types.
RK 512 only: Partner returns incorrect parameters in
message frame header.
CP 341 Point-to-Point Communication, Installation and Parameter Assignment