Siemens Simatic S7-300 CP 341 User Manual page 198

Point-to-point communication, installation and parameter assignment
Table of Contents

Advertisement

Diagnostics with the CP 341
8.1 Diagnostics Functions of the CP 341
Event class 10 (0AH):
"Errors in response message frame of the partner detected by the CP"
(0A)01H
Only for RK 512:
Synchronization error of partner, because:
Response message frame without request
Response message frame received before
continuation message frame sent
Continuation response message frame
received after an initial message frame was
sent
A first response message frame was received
after a continuation message frame was sent
(0A)02H
RK 512 only: Error in the structure of the received
response message frame (1st byte not 00 or FF)
(0A)03H
RK 512 only: Received response message frame
has too many or too few data.
(0A)04H
RK 512 only: Response message frame for SEND
request arrived with data.
(0A)05H
RK 512 only: No response message frame
received from partner within monitoring time.
198
www.gkbpx.com
This error is reported after your own programming
device is restarted in the case of long message
frames or when the partner is restarted. This
represents normal system start-up behavior. You do
not have to correct anything.
The error can also occur during operation as a
consequence of error statuses only recognized by
the partner.
Otherwise, you can assume an error on the part of
the partner device. The error may not occur in the
case of requests < 128 bytes.
Check for malfunction of the partner device, possibly
by using interface test device interconnected in the
data link.
Check for malfunction of the partner device, possibly
by using interface test device interconnected in the
data link.
Check for malfunction of the partner device, possibly
by using interface test device interconnected in the
data link.
Is the partner a slow device? This error is also often
displayed as a consequence of a previous error. For
example, procedure receive errors (event class 8)
can be displayed after a FETCH message frame
was sent. Reason: The response message frame
could not be received because of disturbances. The
monitoring time expires. This error also possibly
occurs if the partner is restarted before it could
respond to the last received FETCH message frame.
CP 341 Point-to-Point Communication, Installation and Parameter Assignment