York OPTIVIEW Operation Manual page 149

Control center for ymc2 a
Table of Contents

Advertisement

FORM 160.78-O2
ISSUE DATE: 5/22/2017
SEIKO Printer
DipSW
1-1 = off
Input-Serial
1-2 = on
Printing speed high
1-3 = on
Auto loading - on
1-4 = off
Auto LF - off
1-5 = on
Setting Command - Enable
1-6 = off
Printing density - 100%
1-7 = on
Printing density - 100%
1-8 = on
Printing, density - 100%
DipSW
2-1 = on
Printing Columns - 40
2-2 = on
User Font Back-up - on
2-3 = on
Character Select - normal
2-4 = off
Zero - slash
2-5 = on
International character set - American
2-6 = on
International character set - American
2-7 = on
International character set - American
2-8 = off
International character set -American
DipSW
3-1 = on
Data length - 8 bits
3-2 = on
Parity Setting - no
3-3 = on
Parity condition - odd
3-4 = on
Busy control - H/W busy
3-5 = on
Baud rate select - 1200*
3-6 = off
Baud rate select - 1200*
3-7 = on
Baud rate select - 1200*
3-8 = off
Baud rate select - 1200*
* Settings shown for 1200 Baud. Other Baud rates can
be selected. Refer to Printer manufacturer's manual
supplied with Printer.
CONTROL CENTER SETUP
Chiller ID
Access Level Required: OPERATOR
Using the COMMS Screen, assign an Identification
number to the chiller. This number will appear at the
top of each report.
JOHNSON CONTROLS
Printer Setup
Access Level Required: OPERATOR
Using the COMMS Screen, the control center must be
configured to transmit data in the same format as the
Printer is configured to receive the data. The following
values must be entered.
• Baud Rate - Set as desired. Value selected must be
the same as Printer configuration above.
• Data Bits - 8
• Parity - None
• Stop Bits - 1
Printer Type
Access Level Required: OPERATOR
Using the PRINTER Screen, the actual Printer type
connected to the control center must be entered. Selec-
tion determines the control codes that are sent to the
Printer. These codes determine such things as lines per
inch, character width and general formatting. Available
selections are: Okidata, Weigh-Tronix and Seiko.
Automatic Data Logging
Access Level Required: OPERATOR
If automatic data logging is desired, a Status Report
can be automatically printed at a specified interval
beginning at a specified time, using the PRINTER
Screen. The interval is programmable over the range of
1 minute to 1440 minutes in 1 minute increments. The
first print will occur at the programmed START time
and occur at the programmed OUTPUT INTERVAL
thereafter. The time remaining until the next print is
displayed on the PRINTER Screen.
• Automatic Printer Logging - Enables and disables
automatic data logging
• Log Start Time ‑ Enter the time the first print is
desired.
• Output Interval - Enter the desired interval be-
tween prints.