Table 6 - Warning Messages - York OPTIVIEW Operation Manual

Control center for ymc2 a
Table of Contents

Advertisement

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION

TABLE 6 - WARNING MESSAGES

MESSAGE
WARNING – MBC – LANDING
COUNTER HIGH
WARNING – MBC – ROTATION
MODE OFF
WARNING – MOTOR – HIGH
CURRENT LIMIT
WARNING – CONDENSER –
HIGH PRESSURE LIMIT
WARNING – CONDENSER OR
EVAPORATOR XDCR ERROR
WARNING – CONDENSER OR
VGD SENSOR FAILURE
WARNING – EVAPORATOR –
LOW PRESSURE LIMIT
116
The MBC landing counter has accumulated 30 events where the motor shaft displace-
ment exceeded 120 µm (80% of the air gap space to the touchdown bearing) while shaft
rotation is detected. This warning is released only when a service technician checks
the shaft air gap measurement for acceptability and resets the MBC according to the
driveline service manual YORK YMC
During the time the MBC Rotation Mode is commanded ON by the microboard via serial
comms this warning is set if the MBC reports Rotation Mode is OFF by serial comms.
This warning is inhibited if MBC communication is not initiated and during the first 15
seconds after the Rotation Mode is commanded ON. This warning is released when
Rotation Mode status matches the microboard command to the MBC.
The chiller motor current is greater than or equal to the Motor Overload current limit.
The Motor Overload current limit is predetermined from the motor model and Maximum
VSD Output Current. While this condition is in effect, chiller capacity control is in over-
ride to reduce current. Normal LCHLT capacity control operation is resumed and this
message automatically clears when the motor current decreases below this limit.
The Condenser Pressure exceeds the High Pressure Warning Setpoint threshold,
programmed by a Service technician logged in at SERVICE access level. While this
condition is in effect, the chiller capacity is in override to reduce pressure. This message
automatically clears and normal LCHLT capacity control restored when the Condenser
pressure decreases to below the Setpoint.
The Evaporator pressure Transducer is indicating a higher pressure than the Condenser
pressure Transducer after the chiller has been running for 10 minutes. This is indicative
of a Condenser or Evaporator Transducer failure. This message will be displayed until
the condition clears and the WARNING RESET Keypad key is pressed in OPERATOR
(or higher) access mode. Condition not checked in Brine mode.
The difference between the Stall Pressure Transducer output (discharge pressure) and
the Condenser Pressure Transducer output has exceeded 0.28 VDC for 3 continuous
minutes while the chiller was running. This feature verifies the operation of the Stall
Transducer and the Condenser transducer. Since both transducers are measuring es-
sentially the same pressure, both outputs should be within the specified tolerance. This
message must be manually cleared. It will be displayed until the transducer outputs are
within the acceptable range of each other and the WARNING RESET key in SERVICE
access level.
While this message is displayed, the Variable Geometry Diffuser (VGD) is driven to the
full open position and held there until this warning is manually cleared. When cleared,
the VGD returns normal operation.
The Evaporator pressure has decreased to the Warning threshold. This threshold is
fixed in Water cooling applications. In Brine cooling applications, the threshold is a fixed
amount above the programmable safety shutdown threshold. The Safety threshold in
Brine applications is determined by the Brine solution and is determined by the YORK
Factory. While this condition is in effect, the chiller capacity control is in override to in-
crease suction pressure. This message automatically clears and normal LCHLT capacity
control restored when the Evaporator pressure increases to the reset value.
EVAPORATOR PRESSURE THRESHOLDS
Warning Threshold
Water
R134a
27.0
DESCRIPTION
Service Manual (Form 160.78-M2).
2
Reset Threshold
(PSIG)
(PSIG)
Brine
Water
+2.0>Safety
+3.0>Safety
28.0
Setpoint
FORM 160.78-O2
ISSUE DATE: 5/22/2017
Brine
Setpoint
JOHNSON CONTROLS