Error Alarms; Sending Text Message In Case Of Error - Samson TROVIS 5474 Mounting And Operating Instructions

Automation system 5400, boiler controller
Table of Contents

Advertisement

Operational faults
9.5

Error alarms

Error alarms can be sent over a modem either directly to the control station or over the SMS text
message function to a mobile phone or to a fax. Just one function (Modbus, SMS function or fax
function) can be selected at one time since the functions use the same interface.
The error alarms to a mobile phone and to a fax contain the number of the affected error status
register (FSR1/FSR2), the fault as per error status register (BitNo), the controller ID and the bit
number (Bit xx).

9.5.1 Sending text message in case of error

Currently, text messages can only be sent to the German D1 network. The corresponding access
numbers into the D1 network as well as the mobile phone number of the recipient must be set in
the PA9 level:
4
D1 access number: 0171 252 10 02
(add 0 in front when dialing from a private branch exchange)
Digits 0 to 9, P = pause, - = end, max. 22 characters
The access number is assigned by Deutsche Telekom and may alter.
4
Mobile phone number: 49 xxx yyyyyyy , where xxx stands for 160, 171 or any other valid
D1 dialing code and yyyyyy represents the specific phone number of the mobile phone you
wish the alarm to be sent to.
Digits 0 to 9, P = pause, - = end, max. 14 characters
Note!
Currently, text messages can only be sent to the German D1 network.
Functions
Modbus
Modem function
Text message alarm to a mobile
phone
SMS dialing procedure
Alarm sent per fax
64
EB 5474 EN
WE
Configuration
ON
Co9 -> Fb00 = OFF
OFF
Co9 -> Fb01 = OFF
OFF
Co9 -> Fb06 = ON
OFF
Co9 -> Fb07
OFF
Co9 -> Fb10 = OFF