Samson TROVIS 5474 Mounting And Operating Instructions page 92

Automation system 5400, boiler controller
Table of Contents

Advertisement

Appendix
Co9: Modbus/meter bus
Fb Function
00 Modbus
01 Modem function
02 Modem dialing
procedure
03 Lock dial-up
04 Modbus
16-bit addressing
05 Reserved
06 Text message alarm
to a mobile phone
07 SMS dialing
procedure
08 Reserved
09 Reserved
10 Alarm sent per fax
11 Fax dialing
procedure
21
Meter 1
to
to
23
Meter 3
Fb = Function block, WE = Default setting, SZ = Key number
92
EB 5474 EN
SZ
WE Function block parameter / Range of values (default setting)
ON Co9 -> Fb00 = ON: Modbus active
only with Co9 -> Fb06 = OFF and Co9 -> Fb10 = OFF
OFF Co9 -> Fb01 = ON: Modem function active
OFF Co9 -> Fb02 = ON: Pulse
Co9 -> Fb02 = OFF: Tone
OFF Co9 -> Fb03 = ON: No dial-up in case an error
Co9 -> Fb03 = OFF: Dial-up in case an error
OFF Co9 -> Fb04 = ON: 16-bit addressing
Co9 -> Fb04 = OFF: 8-bit addressing
OFF Co9 -> Fb06 = ON: Text message alarm to a mobile phone
only with Co9 -> Fb00 = OFF and Co9 -> Fb10 = OFF
OFF Co9 -> Fb07 = ON: Pulse
Co9 -> Fb07 = OFF: Tone
OFF Co9 -> Fb10 = ON: Alarm sent per fax
only with Co9 -> Fb00 = OFF and Co9 -> Fb06 = OFF
OFF Co9 -> Fb11 = ON: Pulse
Co9 -> Fb11 = OFF: Tone
OFF Co9 -> Fb21 = ON: Meter 1 is being processed
to
Co9 -> Fb23 = ON: Meter 3 is being processed
Function block parameters:
Meter bus address for WMZ / 0 to 255 (255)
Model code WMZ / P15, PS2,1434, CAL3, APAtO, SLS (1434)
Reading mode WMZ / 24h, con, CoiL (con)