Brief Operating Instructions
Proline t-mass B 150
Thermal Mass Flow Measuring System
These Instructions are Brief Operating Instructions; they do not replace the
Operating Instructions included in the scope of supply.
For detailed information, refer to the Operating Instructions and other
documentation on the CD-ROM provided or visit www.endress.com/
deviceviewer .
KA01104D/06/EN/01.12
71165082

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Proline t-mass B 150

  • Page 1 Brief Operating Instructions Proline t-mass B 150 Thermal Mass Flow Measuring System These Instructions are Brief Operating Instructions; they do not replace the Operating Instructions included in the scope of supply. For detailed information, refer to the Operating Instructions and other documentation on the CD-ROM provided or visit www.endress.com/...
  • Page 2: Table Of Contents

    Table of contents Proline t-mass B 150 Table of contents 1 Document information ........3 1.1 Document conventions .
  • Page 3: Document Information

    Proline t-mass B 150 Document information Document information Document conventions 1.1.1 Safety symbols Symbol Meaning DANGER DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. A0011189-EN WARNING WARNING This symbol alerts you to a dangerous situation.
  • Page 4 Document information Proline t-mass B 150 1.1.4 Symbols for certain types of information Symbol Meaning Allowed Indicates procedures, processes or actions that are allowed. A0011182 Preferred Indicates procedures, processes or actions that are preferred. A0011183 Forbidden Indicates procedures, processes or actions that are forbidden.
  • Page 5: Basic Safety Instructions

    Proline t-mass B 150 Basic safety instructions Basic safety instructions Requirements for the personnel The personnel must fulfill the following requirements for its tasks: Trained, qualified specialists must have a relevant qualification for this specific function and ► task Are authorized by the plant owner/operator ►...
  • Page 6: Workplace Safety

    Basic safety instructions Proline t-mass B 150 Verification for borderline cases: For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in ► verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
  • Page 7: Product Description

    Proline t-mass B 150 Product description Product description Product design A0017196 Electronics compartment cover Display module Terminal block Electronics module Cable gland Transmitter housing Sensor S-DAT Endress+Hauser...
  • Page 8: Incoming Acceptance And Product Identification

    Incoming acceptance and product identification Proline t-mass B 150 Incoming acceptance and product identification Incoming acceptance A0015502 A0013843 A0013695 A0015502 A0013698 A0015502 A0013699 Endress+Hauser...
  • Page 9: Product Identification

    Proline t-mass B 150 Incoming acceptance and product identification A0015502 A0013697 If one of the conditions does not comply, contact your Endress+Hauser distributor. Product identification The following options are available for identification of the measuring device: • Nameplate specifications • Order code with breakdown of the device features on the delivery note •...
  • Page 10: Storage And Transport

    Storage and transport Proline t-mass B 150 Storage and transport Storage conditions Observe the following notes for storage: • Store in original packaging. • Do not remove the protection cap mounted on the transducer. • Protect from direct sunlight. • Select a storage location where moisture cannot collect in the measuring device.
  • Page 11: Installation

    Proline t-mass B 150 Installation Installation Installation conditions For mechanical reasons and to protect the pipe, support is recommended for heavy sensors (e.g. with a hot-tap retractable assembly). 6.1.1 Mounting position Orientation The direction of the arrow on the sensor helps you to install the sensor according to the flow direction.
  • Page 12 Installation Proline t-mass B 150 Further information ® ISO standard 14511 A0005103 Correctly aligned flanges and seals A0005105 A0005104 A0005106 Incorrectly sized seal Incorrectly aligned flanges and seals Internal diameter of pipe does not correspond to internal diameter of sensor...
  • Page 13 C1 + C2 = 107 mm (4.21 in) DK6MB-CXA mounting boss 3/4 NPT C1 + C2 = 102 mm (4.02 in) Determining C1 and C2 (not limited to Endress+Hauser original parts) Length of pipe connection used C2 (compression fitting with G1A thread) 39 mm (1.54 in)
  • Page 14 Installation Proline t-mass B 150 Mounting conditions for mounting boss 90° 90° A0011843 = 31.0 mm ± 0.05 mm (1.22 in ± 0.02 in) When installing in rectangular ducts with thin walls: ► Ã Use suitable support brackets. Align the insertion version with the direction of flow.
  • Page 15 Proline t-mass B 150 Installation Recommended inlet and outlet runs 20 × DN 5 × DN 20 × DN 5 × DN 20 × DN 5 × DN 25 × DN 5 × DN 50 × DN 5 × DN 40 ×...
  • Page 16: Mounting The Measuring Device

    Installation Proline t-mass B 150 Avoid direct sunlight, particularly in warm climatic regions. System pressure Sensor Depending on the version, please note the details on the name plate . Max. 20 bar g (290 psi g) Thermal insulation A0015763 Mounting the measuring device 6.2.1...
  • Page 17 Proline t-mass B 150 Installation 1. Ensure that the direction of the arrow on the sensor matches the flow direction of the medium. 1½ 30 mm A0017331 Ensure the insertion depth and alignment are correct. Thread adapter nut: when mounting for the first time, tighten it fingertight + 1½...
  • Page 18: Post-Mounting Check

    Installation Proline t-mass B 150 max. 2 × 90° 4 mm 4 mm A0017227 6.2.5 Turning the display module A0017228 Post-mounting check Is the device damaged (visual inspection)? Does the measuring device conform to the measuring point specifications? For example: •...
  • Page 19 Proline t-mass B 150 Installation Has the correct orientation for the sensor been selected (® ä 11)? • According to sensor type • According to medium properties • According to medium temperature • According to process pressure Does the arrow on the sensor match the direction of flow of the medium through the piping (®...
  • Page 20: Electrical Connection

    Electrical connection Proline t-mass B 150 Electrical connection Connection conditions 7.1.1 Required tools • For cable entries: Use corresponding tools • Wire stripper • When using stranded cables: Crimping tool for wire end ferrule • Flat blade screwdriver£ 3 mm (0.12 in) 7.1.2...
  • Page 21: Connecting The Measuring Device

    Proline t-mass B 150 Electrical connection 7.1.4 Terminal assignment The terminal assignment for the electrical connection can be found on the nameplate of the electronics module. Power Supply DC 24 V L– – Pulse/freq./ switch output – 4…20 mA HART –...
  • Page 22: Ensuring The Degree Of Protection

    Electrical connection Proline t-mass B 150 7.2.1 Connecting the cables 20 mm 3 (0.12) – 10 (0.4) mm (in) A0017250 NOTICE! Housing degree of protection voided due to insufficient sealing of the housing. ► Screw in the thread without using any lubricant. The threads on the cover are coated with a dry lubricant.
  • Page 23: Post-Connection Check

    Proline t-mass B 150 Electrical connection 2. Tighten all housing screws and screw covers. 3. Firmly tighten the cable glands. 4. To ensure that moisture does not enter the cable entry, route the cable so that it loops down before the cable entry ( water trap ).
  • Page 24: Operation Options

    Operation options Proline t-mass B 150 Operation options Structure and function of the operating menu 8.1.1 Structure of the operating menu Operating menu for operators and maintenances Language Display/operat. Setup Diagnostics Operating menu for experts Expert A0014058-EN Endress+Hauser...
  • Page 25 Proline t-mass B 150 Operation options 8.1.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles. Each user role contains typical tasks within the device lifecycle. For detailed information about the operating philosophy of the instrument, refer to the...
  • Page 26: Access To The Operating Menu Via The Local Display

    Operation options Proline t-mass B 150 Access to the operating menu via the local display A0014013 Operational display with measured value shown as "1 value, max." (example) 1.1 Device tag 1.2 Display area for measured values (4-line) 1.3 Explanatory symbols for the measured value: measured value type, measuring channel number, symbol for event behavior 1.4 Status area...
  • Page 27 Proline t-mass B 150 Operation options 8.2.1 Operational display Status area Status signals A0013956 A0013959 A0013958 A0013957 Failure Function check Out of specification Maintenance required Diagnostic behavior Locking Communication A0013961 A0013962 A0013965 A0013963 Alarm Warning Device locked Remote operation enabled...
  • Page 28 Operation options Proline t-mass B 150 Display area Icons for menus A0013974 A0013975 A0013966 A0013973 Display/operat. Setup Diagnostics Expert Icons for submenus, wizards, parameters Lock symbols A0013967 A0013968 A0013972 A0013963 Submenu Wizard Parameters within a wizard Parameter locked 8.2.3 Editing view...
  • Page 29 Proline t-mass B 150 Operation options 8.2.4 Operating elements Meaning Minus key In a menu, submenu Moves the selection bar upwards in a choose list. With a Wizard Confirms the parameter value and goes to the previous parameter. A0013969 With a text and numeric editor In the input mask, moves the selection bar to the left (backwards).
  • Page 30 Operation options Proline t-mass B 150 Meaning Minus/Enter key combination (press the keys simultaneously) Reduces the contrast (brighter setting). A0013953 Plus/Enter key combination (press and hold down the keys simultaneously) Increases the contrast (darker setting). A0013954 Minus/Plus/Enter key combination (press the keys simultaneously) For operational display Enables or disables the keypad lock.
  • Page 31 Proline t-mass B 150 Operation options Calling up and closing the help text The user is in the navigation view and the selection bar is on a parameter. 1. 2 s Press F for à The help text for the selected parameter opens.
  • Page 32: Access To The Operating Menu Via The Operating Tool

    Operation options Proline t-mass B 150 8.2.9 Enabling and disabling the keypad lock The keypad lock makes it possible to block access to the entire operating menu via local operation. As a result, it is no longer possible to navigate through the operating menu or change the values of individual parameters.
  • Page 33: Commissioning

    Proline t-mass B 150 Commissioning A0017373 å 2 Options for remote operation via HART protocol Control system (e.g. PLC) Field Communicator 475 Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM) Commubox FXA195 (USB) Field Xpert SFX100 VIATOR Bluetooth modem with connecting cable...
  • Page 34: Setting The Operating Language

    Commissioning Proline t-mass B 150 Setting the operating language Factory setting: English or ordered local language X X X X X X X 20.50 Main menu 0104-1 Language English Display/operat. Setup Language 0104-1 English à Deutsch Español Français Language 0104-1 Ã...
  • Page 35: Defining The Tag Name

    Proline t-mass B 150 Commissioning ® Pipe shape ® Pipe inner diameter ® Duct internal height ® Duct internal width ® Installation factor ® Assign current output ® 4mA value ® 20mA value ® Operating mode Pulse Frequency Switching output...
  • Page 36: Protecting Settings From Unauthorized Access

    Commissioning Proline t-mass B 150 User entry Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /) In the factory configuration, the tag name appears at the top left in the header. Protecting settings from unauthorized access...
  • Page 37: Diagnostic Information And Remedial Measures

    Proline t-mass B 150 Diagnostic information and remedial measures – A0017255 1. Unscrew the electronics compartment cover. 2. Pull out the display module with a gentle rotational movement. 3. To make it easier to access the lock switch, attach the display module to the edge of the electronics compartment.
  • Page 38 Diagnostic information and remedial measures Proline t-mass B 150 X X X X X X X X X X X X X X 20.50 S441 Curr. output 1 Curr. output 1 (ID:153) S441 2d11h05m55s 1. Check process 2. Check current output settings A0013940-EN å...
  • Page 40 KA01104D/06/EN/01.12 71165082...