Troubleshooting for Outdoor Unit
7.8
Compressor Lock
E6
Error Code
Outdoor Unit LED
A j 1 h 2 i 3 i 4 h 5 h
Display
Method of Error
A compressor lock is detected by checking the compressor running condition through the position
Detection
detection circuit.
Error Decision
Judging from the current waveform generated when high-frequency voltage is applied to the
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Closed stop valve
Causes
Defective outdoor unit PCB
Defective compressor
Defective electronic expansion valve
208
compressor.
SiUS121827E
Part 6 Service Diagnosis