7.13 High Pressure Control in Cooling
F6
Error Code
Outdoor Unit LED
A j 1 i 2 h 3 i 4 i 5 h
Display
Method of Error
High pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
Detection
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Error Decision
The temperature sensed by the outdoor heat exchanger thermistor rises above about 62.5°C
Conditions
The error is cleared when the temperature drops below about 49.5°C (121.1°F).
Supposed
The installation space not large enough
Causes
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB