Chamberlain Elite CSW200501UL Installation Manual page 43

Commercial high-traffic ac swing gate operator
Table of Contents

Advertisement

Code
Meaning
CLOSE EYE/INTERRUPT triggered, causing
70
reversal, preventing close, or resetting TTC
CLOSE EDGE triggered, causing reversal, NO
71
preventing close, or canceling TTC
OPEN EYE/EDGE triggered, causing reversal or
72
preventing opening
CLOSE EYE/INTERRUPT triggered, causing
73
reversal, preventing close, or resetting TTC
CLOSE EYE/EDGE triggered, causing reversal and
74
preventing close or canceling TTC
OPEN EYE/EDGE triggered, causing reversal or
75
preventing opening
Close input (EYE/EDGE) communication fault from
80
other operator
Open input (EYE/EDGE) communication fault from
81
other operator
Close input (EYE/EDGE) communication fault
82
(expansion board)
Open input (EYE/EDGE) communication fault
83
(expansion board)
Non-monitored device detected on the wireless
84
safety system
91
Force Reversal (Operator 1)
93
RPM / STALL Reversal (Operator 1)
95
AC motor no start condition
96
Current Sensor Fault
99
Normal Operation
TROUBLESHOOTING
Solution
IF an obstruction occurred, no action required. If an obstruction did NOT
occur, check alignment, inputs, and wiring on main control board
IF an obstruction occurred, no action required. If an obstruction did NOT
occur, check alignment, inputs, and wiring on expansion board.
Check inputs and communication method between operators, either wired
bus or radio. Ensure operator is powered. May have to erase the wireless
communication and reprogram the two operators.
Check the connections between the main board and the expansion board.
Non-monitored contact closure devices are not supported. Make sure
connected devices are monitored. Check edges for proper orientation and
resistive end cap connection.
Check for obstruction. If no obstruction, check that the mechanical
assembly is engaged and free to move. See section on Limit and Force
Adjustment, and Obstruction Test.
Check for obstruction. If no obstruction, check the operator wiring and
that the mechanical assembly is engaged and free to move. Replace APE
assembly.
Motor start sequence failed. If the gate and motor are NOT moving, or
moving too slow, check for an obstructed gate, binding in the mechanism,
and relay board and start capacitor connections. If the gate and motor ARE
moving, failure is due to loss of the encoder signal. Check the encoder
cup and sensor on the limit shaft, and wiring.
A fault was detected on the current sensor. Make sure the current sensor is
connected to the main control board. Check the current sensor harness for
an open or short. The operator will need a power cycle to resume
operation after correcting the fault. If the fault continues, replace the power
board.
No action required
43
Saved
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES