Chapter 6
Certification
Section 6.1.8
Other Approvals
This device meets the requirements of the following additional standards:
• EN50121-4
Railway applications – Electromagnetic Compatibility – Emission and Immunity of the Signaling and
Telecommunications Apparatus
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS900GP has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-12
34
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
Earth
Ground Ports
Signal Ports
± 500 V Line-to-Earth
± 500 V Line-to-Line
DC Power Ports
± 500 V Line-to-Earth
± 500 V Line-to-Line
Signal Ports
DC Power Ports
Earth
Ground Ports
Enclosure Ports
DC Power Ports
Signal Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
DC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
Test Levels
± 8 kV
± 15 kV
20 V/m
± 1.5 kV
± 2 kV
10 V
10 V
10 V
40 A/m Continuous
1000 A/m for 1 s
30% for 0.1 s
60% for 0.01 s
100% for 0.01 s
RUGGEDCOM RS900GP
Installation Guide
Severity Levels
4
4
x
3
x
3
x
x
3
3
3
3
3
Other Approvals