26
PRESSURE DROP
20
FLOW RATE Boiler heat losORIGINAL
gpm
Feet w.c
DATA
Head
(feet w.c.)
28
16
14.53
15
23.4
11.77
11.77
20.04
9
8.77
17.55
7.38
7.38
14.04
5.3
5.3
11.7
4.2
3.46
10
0
0
0
column modified
5
8/25/2007
0
0
5
Figure 18. Boiler water side pressure drop
Flow
Temp
Rate
Rise
(gpm)
(˚F)
28.0
25˚
23.5
30˚
20.0
35˚
17.5*
40˚
Table 2. Jaguar boiler recommended pump models for domestic hot water tank piping.
Notes:
* This is the minimum flow rate recommended for Jaguar boiler.
** Domestic water tank piping head is based on 1" inside diameter piping and full port valves.
*** Refer to the DHW Tank Manufacturer's water flow rate requirements and associated pressure drop head loss, to select
the appropriate circulator.
If 2 circulators are specified, they must be piped in series in order to provide the head capacity shown. Power to
circulator(s) must be supplied through an appropriate relay to protect the boiler control's fuse.
JAGUAR
10
15
20
Flow Rate (GPM)
Boiler
Domestic Water
Head
Tank Piping
Loss
Head Loss **
(Feet w.c.)
(Feet w.c.)
16
6.5
11.5
6.0
8.5
5.5
7.0
5.0
25
30
Available Head Capability for Various Model
Circulators to Overcome DHW Tank Head Loss
Taco 1400-20
Not Recommended
Not Recommended
9.0
11.5
Jaguar Model J-390
(Feet w.c.) ***
(2 in series)
Taco 1400-45
Taco 1400-20
4.5
11.5
18.0
21.5
9.5
20.5
32.0
35.0