Download Print this page

Slant/Fin Caravan GGHT-1050 Specification Sheet

Modular boiler submittal data ggt series—gas-fired/hot water
Hide thumbs Also See for Caravan GGHT-1050:

Advertisement

GGT SERIES—Gas-Fired/Hot Water
A Caravan modular boiler system consists of two
or more compact cast-iron boilers that offer
significant advantages in terms of installed cost,
efficiency and reliability. Caravan systems are
based on step-firing just enough modules to meet
heating demands. GGT systems are available in
400,000 to multi-million Btuh gross input. For
additional information, see Caravan Engineering
Manual, pub. C-30 and Caravan gas application
guide, pub. CG-10-HWG.
Standard Equipment
One per module unless otherwise noted:
Pre-assembled cast-iron heat exchanger with
built-in air separators and insulated jacket.
Base.
Flue collector.
Gas burners, gas orifices and manifold assembly.
Combination gas valve including manual shut-off
and pressure regulator.
Pilot adjustment and automatic pilot
thermocouple safety.
Hi-limit control.
Ratings
Gas Caravan ratings and dimensions/hot water models — GGT Series
Consists of
No. of
Module
Htg.
Model
Model No. *
Mod.§
Number
GGT-400
2
GG-200EC
GGT-500
2
GG-250EC
GGT-600
2
GG-300EC
GGHT-700
2
GG-350HEC
GGHT-750
2
GG-375HEC
GGHT-800
2
GG-399HEC
GGT-900
3
GG-300C
GGHT-1050
3
GG-350HEC 1050
GGHT-1125
3
GG-375HEC 1125
GGHT-1200
3
GG-399HEC 1197
GGT-1200
4
GG-300C
GGHT-1400
4
GG350HEC
GGHT-1500
4
GG-375HEC 1500
GGT-1500
5
GG-300EC
GGHT-1600
4
GG-399HEC 1596
GGHT-1750
5
GG-350HEC 1750
GGHT-1875
5
GG-375HEC 1875
GGHT-2000
5
GG-399HEC 1995
GGHT-2100
6
GG-350HEC 2100
GGHT-2250
6
GG-375HEC 2250
GGHT-2400
6
GG-399HEC 2394
GGHT-2450
7
GG-350HEC 2450
GGHT-2625
7
GG-375HEC 2625
GGHT-2800
7
GG-399HEC 2793
GGHT-2800
8
GG-350HEC 2800
GGHT-3000
8
GG-375HEC 3000
GGHT-3150
9
GG-350HEC 3150
GGHT-3200
8
GG-399HEC 3192
GGHT-3375
9
GG-375HEC 3375
GGHT-3500
10
GG-350HEC 3500
GGHT-3600
10
GG-399HEC 3591
GGHT-3750
10
GG-375HEC 3750
GGHT-4000
10
GG-399HEC 3990
FOR LARGER SIZES, USE MULTIPLES OF THE ABOVE.
Modular Boiler Submittal Data
®
Module pressure and tempera-
ture gauge (unmounted).
Module pressure relief valve
(ASME) (unmounted). Specify 30,
50 or 100 psi.
Control header (unmounted, one
per system).
Draft hood (unmounted).
Spark ignition system.
I=B=R Ratings
I=B-R
(MBH)
EDR
Net
Gross
Water‡
Output†
Input
Output§
(Sq. Ft.)
(MBH)
400
332
1866
280
500
402
2333
350
600
480
2780
417
700
581
3368
505
750
608
3520
528
798
654
3786
568
900
720
4173
626
872
5052
758
912
5286
793
981
5686
853
1200
960
5560
834
1400
1162
6736
1010
1216
7046
1057
1500
1200
6950
1043
1308
7580
1137
1453
8420
1263
1520
8806
1321
1635
9473
1421
1743
10104
1516
1824
10573
1586
1962
11373
1706
2034
11788
1768
2128
12333
1850
2289
13266
1990
2324
13472
2021
2432
14093
2114
2615
15157
2273
2616
15160
2274
2736
15860
2379
2905
16841
2526
2943
17060
2559
3040
17620
2643
3270
18953
2843
Optional Equipment
Hot water supply and return header
Control panel with automatic lead/lag.
Standing pilot available on:
Vent dampers.
External DHW heat exchanger.
Boiler
Water
A.G.A.
Horse-
Content
Combust.
Ship
power
(gal.)
Efficiency
9.9
14.2
82.0
12.0
16.4
80.4
14.3
18.4
80.0
1080
17.3
20.6
83.0
1230
18.1
20.6
81.0
1230
19.5
20.6
82.0
1230
21.5
27.6
80.0
1590
26.0
30.9
83.0
1830
27.2
30.9
81.0
1830
29.3
30.9
82.0
1830
28.7
36.8
80.0
2140
34.7
41.2
83.0
2440
36.3
41.2
81.0
2440
35.9
46.0
80.0
2675
39.0
41.2
82.0
2440
43.4
51.5
83.0
3050
45.4
51.5
81.0
3050
48.8
51.5
82.0
3050
52.0
61.8
83.0
3660
54.4
61.8
81.0
3660
58.6
61.8
82.0
3660
60.7
72.1
83.0
4270
63.5
72.1
81.0
4270
68.3
72.1
82.0
4270
69.4
82.4
83.0
4880
72.6
82.4
81.0
4880
78.1
92.7
83.0
5490
78.1
82.4
82.0
4880
81.7
92.7
81.0
5490
86.8
103.0
83.0
6100
87.9
92.7
82.0
5490
90.8
103.0
81.0
6100
97.6
103.0
82.0
6100
assemblies.
GG-200EC, GG-250EC, GG-300EC
Wt.
820
950
* Specify gas by name, "Natural" or
"Propane".
† Net ratings are based on piping and
pick-up allowance of 1.15. Slant/Fin
should be consulted before selecting
a boiler for installation having unusual
piping and/or pick-up requirements.
Ratings must be reduced by 4% at
2,000 ft. elevation and an additional
4% for every additional 1,000 ft.
elevation over 2,000 ft.
‡ Net ratings in square feet based on
emission rate of 150 Btuh/sq. ft.
§ I=B=R gross output.
Modules in excess of 10 should be
piped in parallel in two or more
batteries. For dimension
specifications, refer to Publication
number CG-10-HWG.
Note: Specify pressure relief setting.
Relief valve is available with
30, 50 or 100 psi.

Advertisement

loading

Summary of Contents for Slant/Fin Caravan GGHT-1050

  • Page 1 Gas burners, gas orifices and manifold assembly. Combination gas valve including manual shut-off and pressure regulator. Pilot adjustment and automatic pilot thermocouple safety. Hi-limit control. Ratings Gas Caravan ratings and dimensions/hot water models — GGT Series Consists of I=B=R Ratings (MBH) No. of Module Htg.