6.

Installation

Installation and commissioning must only be carried out by qualified electrical experts.
The recommended local and national safety regulations should be complied with.
To carry out an energy measurement, a meter must be attached between the grid feed-
in point and the solar inverter (in accordance with all local and national safety regula-
tions).
By means of the integrated anti-islanding protection, the function of the recommended
section switch is fulfilled in accordance with all local and national safety regulations.
For details, please see
Caution: The secondary short-circuit current rating is increased at the transfer connec-
tion point to the public electricity supply system by the nominal current of the connected
solar inverter.
7.

Installation of equipment

7.1

Installation location

Install the device on a non-flammable support base.
Avoid installation on resonating bodies (light construction walls etc.).
Installation is possible both indoors and in protected outdoor areas.
An increased ambient temperature can reduce the efficiency of the PV system.
The inverter may produce moderate noise during operation. Please select installa-
tion location with care.
Ensure legibility of the LEDs and the display (check read-off angle and installation
height).
Although the unit is fitted with UV resistant components, direct exposure to sunlight
should be avoided.
Despite having an IP65 enclosure and being certified in accordance with soiling
category III, the unit must not be allowed to become heavily soiled.
Dusty conditions can impair the unit's performance.
NOTE
According to the Australian / New Zealand Standard AS/NZS
5033:2005 (§ 3.1), PV arrays for installation on domestic dwellings in
Australia or New Zealand shall not have maximum voltages greater
than 600 V.
10
„10. Technical data", page
34.