Glycol Correction Factors - York YCAV0157-0267 Installation Operation & Maintenance

60 hz air-cooled screw liquid chillers (150-260 tons). e/v high efficiency and s/p standard efficiency
Table of Contents

Advertisement

The cooler is designed in accordance with ARI-
590-92 which allows for an increase in pressure
drop of up to 15% above the design value shown
on page 40. Debris in the water may also cause
additional pressure drop.
When using glycol solutions, pressure drops are
higher than with water (see correction factors to be
applied when using glycol solutions). Special care
must be taken not to exceed the maximum flow
rate allowed.
A= Correction Factor
B= Mean Temperature through Cooler
C= Concentration W/W
Excessive flow, above the max. GPM,
will damage the evaporator.
JOHNSON CONTROLS

GLYCOL CORRECTION FACTORS

A
A
GLYCOL CORRECTION FACTORS
ETHYLENE GLYCOL
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05
-10
-8
-6
-4
-2
0
B
PROPYLENE GLYCOL
18
17
16
15
14
13
12
11
10
-10
-8
-6
-4
-2
0
B
FORM 201.21-NM1 (616)
50%
40%
C
30%
20%
10%
2
4
6
8 C
50%
40%
30%
C
20%
10%
2
4
6
8 C
LD10500
41
6