Chilled Liquid & Suction Temp Sensor Input Voltage Table - York YCAV0157-0267 Installation Operation & Maintenance

60 hz air-cooled screw liquid chillers (150-260 tons). e/v high efficiency and s/p standard efficiency
Table of Contents

Advertisement

MAINTENANCE
CHILLED LIQUID AND SUCTION TEMPERATURE
TABLE 30 - TEMPERATURE INPUT VOLTAGE SENSOR (MEASURED SIGNAL TO SHIELD AT THE SENSOR)
TEMP. (ºF)
VOLTAGE
16.1
16.7
17.3
17.9
18.5
19.1
19.7
20.3
20.9
21.5
22.1
22.7
23.3
23.9
24.5
25.0
25.6
26.2
26.8
27.3
27.9
28.5
29.0
29.6
30.2
30.8
31.3
31.9
32.5
33.0
33.6
34.2
34.8
35.3
298
SENSOR INPUT VOLTAGE
TEMP. (ºF)
1.52
35.9
1.54
36.5
1.56
37.0
1.58
37.6
1.60
38.2
1.62
38.7
1.64
39.3
1.66
39.9
1.68
40.4
1.70
41.0
1.72
41.6
1.74
42.1
1.76
42.7
1.78
43.3
1.80
43.9
1.82
44.4
1.84
45.0
1.86
45.6
1.88
46.2
1.90
46.7
1.91
47.3
1.93
47.9
1.95
48.5
1.97
49.1
1.99
49.7
2.01
50.3
2.03
50.8
2.05
51.4
2.07
52.0
2.09
52.6
2.11
53.2
2.13
53.8
2.15
54.5
2.17
55.0
VOLTAGE
TEMP. (ºF)
2.19
55.6
2.21
56.3
2.23
56.9
2.25
57.5
2.27
58.1
2.29
58.7
2.30
59.4
2.32
60.0
2.34
60.6
2.36
61.3
2.38
61.9
2.40
62.5
2.42
63.2
2.44
63.8
2.46
64.5
2.48
65.1
2.50
65.8
2.52
66.5
2.54
67.1
2.56
67.8
2.58
68.5
2.60
69.2
2.62
69.9
2.64
70.6
2.66
71.3
2.68
72.0
2.70
72.7
2.71
73.4
2.73
74.2
2.75
74.9
2.77
2.79
2.81
2.83
FORM 201.21-NM1 (616)
VOLTAGE
2.85
2.87
2.89
2.91
2.93
2.95
2.97
2.99
3.01
3.03
3.05
3.07
3.09
3.11
3.13
3.14
3.16
3.18
3.20
3.22
3.24
3.26
3.28
3.30
3.32
3.34
3.36
3.38
3.40
3.42
JOHNSON CONTROLS