Program Values - York YCAV0157-0267 Installation Operation & Maintenance

60 hz air-cooled screw liquid chillers (150-260 tons). e/v high efficiency and s/p standard efficiency
Table of Contents

Advertisement

Remote Temperature Reset
One of the 5 messages below indicates whether remote
temperature reset was active or disabled at the chiller
keypad at the time of the fault. If active, the type of reset
signal selected is indicated. If the option is not factory
enabled, the option will not appear.
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
DISABLED
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
0.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
2.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
0.0 TO 20.0 MILLIAMPS
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
4.0 TO 20.0 MILLIAMPS
Low Ambient Temp Cutout
OPTIONS
LOW AMBIENT TEMP CUTOUT
◄ ►
XXXXXXXXXXXXXXXXXXXX
This message indicates whether the low ambient cutout
was enabled or disabled at the time of the fault.
Remote Current Reset
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
DISABLED
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
0.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
2.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
0.0 TO 20.0 MILLIAMPS
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
4.0 TO 20.0 MILLIAMPS
JOHNSON CONTROLS
HISTORY KEY (CON'T)
This message indicates whether remote current reset
was active or disabled at the chiller keypad at the time
of the fault and if active, the type of reset signal selected.
One of the following messages will be indicated: DIS-
ABLED (no signal), 0-10VDC, 2-10VDC, 0-20ma, and
4-20ma. If the option is not factory enabled, the option
will not appear.

PROGRAM VALUES

Suction Pressure Cutout
This message indicates the he suction pressure cutout
programmed at the time of the fault.
PROGRAM
SUCTION PRESSURE CUTOUT = XXX.X PSIG
Low Ambient Cutout
This message displays the low ambient temp cutout
programmed at the time of the fault.
PROGRAM
LOW AMBIENT TEMP CUTOUT = XXX.X °F
Low Leaving Chilled Liquid Temp Cutout
This message displays the low leaving Chilled liquid
temperature cutout programmed at the time of the
fault.
PROGRAM
LEAVING LIQUID TEMP CUTOUT = XXX.X °F
Motor Current Limit
This message indicates the motor current limit pro-
grammed at the time of the fault.
PROGRAM
MOTOR CURRENT LIMIT
FORM 201.21-NM1 (616)
8
= XXX %FLA
243