FX2NC Series Programmable Controllers
6.2.1

Reliability tests

The test results in table 6.4 were gathered from a 1 sec ON/OFF test cycle. Please note that
the over current induced by in-rush greatly reduces the relay contacts service life. The rated life
for an inductive AC load such as a contactor or solenoid valve is 500,000 operations at 20VA.
Table 6.5 :
Load capacity
Life of contact (cycles)
Example load (Mitsubishi contactor)
20VA
0.2A/100VAC
0.35A/100V AC
0.1A/200VAC
0.17A/240V AC
3,000,000
1,000,000
S-K10 to S-K95
S-K100 to S-K150
35VA
80VA
0.8A/100V AC
0.4A/240V AC
200,000
S-K180,S-K400
6-6
Outputs 6.