FX2NC Series Programmable Controllers
6.2

Relay output specification

Table 6.4 :
Switched voltages (resistive load)
Rated current / N points (resistive load)
Max. Inductive load
Max. lamp load (tungsten load)
Minimum load
Response time (approx.)
Circuit isolation
Operation indication
≤ 240V AC, ≤ 30V DC
FX
:Main units and Extension blocks
2NC
2A/1point, 4A/1COM(8A/2COM)
(See sec, 3.13, 6.2.2)
FX
,FX
2N
2A/1point, 8A/COM
80VA See table 6.5
100W (1.17A/85V AC, 0.4A/250V AC)
When supply voltage < 24V DC allow at least 5mA flow
OFF
ON
10ms
10ms
ON
OFF
by relay
LED is lit when coil is energized