7.7

Error registers

D8000
Watchdog timer
(default 200msec)
PLC version
M8001
24201=FX
(24=FX
Memory capacity
M8002
02=2K steps, 04=4K steps,
08=8K(16K) steps
Memory type
M8003
02H=EEPROM protect switch OFF
0AH=EEPROM protect switch ON
10H=MPU memory
Error flag number
M8004
8060=M8060, (8060-8068)
Battery voltage
M8005
36=3.6V (uniits 0.1V)
D8006
Low battery detection level
(default 3.0V)
Number of momentry power
D8007
failures - reset on full power OFF
/FX
V2.01
2NC
2N
/FX
, 201=V2.01)
2NC
2N
Power failure detection period
D8008
(Automatically corrected)
Lowest device affected by 24V
D8009
DC power failure
Diagnostics 7.