Omron SYSMAC 3G8F7-CLK13-E Operation Manual page 176

Controller link support boards for pci bus
Table of Contents

Advertisement

Handling Precautions
1,2,3...
Note
1,2,3...
156
The following procedure can be used to automatically set the network param-
eters in EEPROM from other nodes operating on the network. The data link
tables will need to be reset from the Controller Link Support Software.
1. Turn OFF the power supply to the computer of the Board to be replaced.
2. Detach the communications cables attached to the Controller Link Support
Board to be replaced and remove the Board.
3. Set the new Controller Link Support Board's ID switch and the terminating
resistance switch to the same as for the previous Board.
4. Mount the Controller Link Support Board in the expansion slot of the com-
puter and connect the communications cables.
5. Turn ON the power supply to the computer where the Board was replaced
and open the FinsGateway settings.
6. Use the following procedure to set the Board as a polled node.
a. Click the Basic Tab in the FinsGateway Settings.
b. Click the Drivers Icon.
c. Select CLK (PCI) and click the Properties Button.
d. Select the Board to be set and click the Change Button.
e. Click the Driver Tab in the Controller Link (PCI) Lists Dialog Box.
f.
Remove the check from the setting for the polling unit.
g. Click the OK Button.
7. Use the following procedure to start the Controller Link (PCI) service from
the FinsGateway Settings so the Board will participate in the network.
a. Click the Basic Tab in the FinsGateway Settings.
b. Click the Services Icon.
c. Select CLK (PCI) and click the Start Button.
8. Using the CLK Data Link Setting Utility in the FinsGateway or the Control-
ler Link Support Software, read the network parameters and make sure the
Network is operating normally.
9. Using the CLK Data Link Setting Utility in the FinsGateway or the Control-
ler Link Support Software, register data link tables and routing tables in the
new Board.
10. Change the Board to the polling node from the FinsGateway Settings, re-
versing the procedure in step page 156, above. The RUN and INS indica-
tors should light on the Board. The LNK indicator may also light.
11. Check that the data links are operating normally by using the CLK Data
Link Setting Utility in the FinsGateway or the Controller Link Support Soft-
ware.
The following procedure can be used to start the CLK Data Link Setting Utility
in FinsGateway.
1. Click the Basic Tab in the FinsGateway Settings.
2. Click the Networks Icon.
3. Select the desired Board and click the Properties Button.
4. Click the Data Links Tab.
5. Click the Set Data Links Tab.
Refer to FinsGateway online help for details.