Example Of Automatic Setting With Equality Layout - Omron SYSMAC 3G8F7-CLK13-E Operation Manual

Controller link support boards for pci bus
Table of Contents

Advertisement

Setting Data Links
IBM PC/AT or
compatible
Note
5-2-5

Example of Automatic Setting with Equality Layout

DM Parameter Area
Settings
The startup node is the node from which the data links are activated. When
automatically setting data links, data link operation is based on the values set
in the startup node.
Programming Console
Controller Link
Support Software
1. Parameters for automatically setting data links can only be set in PCs. Re-
fer to the Controller Link Units Operation Manual (W309) for details.
2. A computer (Controller Link Support Board) cannot be the startup node for
an automatically setting data links.
3. A computer can participate in automatically set data links created using
1:N allocations with equality layout. Data link tables are not required in the
computer (the data link tables in the startup node will be used).
4. Refer to the Controller Link Units Operation Manual (W309) for details on
automatically setting data links with 1:N allocations.
This section shows an example of DM parameter area settings and the data
link areas that are created as a result.
Set the parameters in the startup node as follows:
CPU Unit
Startup node
Or
Controller Link
DM parameter area
Data link mode: Automatic
Area 1 data link start word: LR 00
Number of words: 10
Area 2 data link start word: DM 1000
Number of words: 200
First data link status word: IR 310
Participating nodes: #1, #2, and #3
Section 5-2