(N) Operation via communication and its settings
CAUTION
 When Pr.502 = "3" and a communication line error occurs, or Pr.502 = "4" and a communication line
error or a communication option fault occurs, the operation continues. When setting "3 or 4" in
Pr.502, provide a safety stop countermeasure other than via communication. For example, input a
signal (RES, MRS, or X92) through an external terminal or press the PU stop on the operation panel.
Error reset operation selection at inverter fault (Pr.349)
• In the External operation mode or the PU operation mode, use this parameter to disable an error reset command sent
through the Ethernet network (CC-Link IE Field Network Basic) or from a communication option.
Pr.349 setting
0 (initial value)
Error reset is enabled independently of operation mode
1
Error reset is enabled only in the network operation mode
Operation mode switching and communication startup mode (Pr.79,
Pr.340)
• Check the following before switching the operation mode.
- The inverter is at a stop.
- Both the STF and STR signals are off.
- The Pr.79 Operation mode selection setting is correct. (Check the setting on the operation panel of the inverter.)
• The operation mode at power ON and at restoration from instantaneous power failure can be selected. Set a value other
than "0" in Pr.340 Communication startup mode selection to select the Network operation mode.
• After the inverter starts up in the Network operation mode, parameter write can be commanded via the network.
NOTE
• The changed value in Pr.340 is applied after the next power-ON or inverter reset.
• The Pr.340 setting can be changed on the operation panel in any operation mode.
• When setting a value other than "0" in Pr.340, make sure that the communication settings of the inverter are correct.
Parameters referred to
Pr.7 Acceleration time, Pr.8 Deceleration time
Pr.79 Operation mode selection
Pr.340 Communication startup mode selection
Pr.550 NET mode operation command source selection
Pr.551 PU mode operation command source selection
Pr.1431 Ethernet signal loss detection function selection
Pr.1432 Ethernet communication check time interval
18
PARAMETER
Description
Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter
Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter
Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter
page 9
page 9
page 19
page 19

Advertisement

Table of Contents
loading

This manual is also suitable for:

F800-e

Table of Contents