Configure Logical Outputs - Honeywell Stryker VAV Operating Manual

Zio configuration
Table of Contents

Advertisement

STRYKER VAV ZIO CONFIGURATION
Display
0d10
0 to 10 volts (Wall Mod LED)
10d0
10 to 0 volts
2d10
2 to 10 volts
10d2
10 to 2 volts
0A20
0 to 20 ma
20A0
20 to 0 ma
0A22
0 to 22 ma
22A0
22 to 0 ma
4A20
4 to 20 ma
20A4
20 to 4 ma
dIG
Binary output (0 and 10 vdc)
255--
none
CONFIGURE LOGICAL
OUTPUTS
Parameter Group Name
Configure Reheat Stage 1 [nciLogicalOutVav, HtgStg1]
63-2730—01
Description
Display
AO_1
Analog output 1
AO_2
dO_1
Binary output 1
dO_2
dO_3
dO_4
--
None
NOTES:
1.
If you select dO_1 or dO_2, verify that
Float_2_TRVL_SEC =0. This frees dO_1 & dO_2
from internal links to Float_2.
2.
If you select dO_3 or dO_4, verify that
Float_1_TRVL_SEC =0. This frees dO_3 & dO_4
from internal links to Float_1.
Same settings as RH STG1
Same settings as RH STG1
Configure modulating reheat [nciLogicalOutVav, ReheatMod]