25. Monitor AIRFLOW value for stability at the maximum
airflow setpoint value.
26. Navigate to PARAMETERS, BALANCE, MAXFLOSP
27. Set the maximum measured flow setpoint: MAXFLOSP
= Avg(AIRFLOW)
28. After the airflow has settled to a stable value, measure
the actual airflow with a calibrated instrument.
29. Navigate to PARAMETERS, BALANCE, MAX_FLOW
30. Set the measured minimum flow calibration value:
MAX_FLOW = measuredValue
31. Navigate to PARAMETERS, OVERRIDE, FLO_OVRD
32. Return system to normal: FLO_OVRD = ----
Parameter Group Name
Offset value to the factory K factor [nciBalanceSetPts,
KFactorOffset]
Maximum airflow setpoint at calibration [nciBalanceSetPts,
MaxMeasFlowSpt]
STRYKER VAV ZIO CONFIGURATION
Measured maximum airflow [nciBalanceSetPts,
MaxMeasFlowAct]
Minimum airflow setpoint at calibration [nciBalanceSetPts,
MinMeasFlowSpt]
Measured minimum airflow [nciBalanceSetPts,
MinMeasFlowAct]
15
63-2730—01