Control Configuration - Honeywell Stryker VAV Operating Manual

Zio configuration
Table of Contents

Advertisement

STRYKER VAV ZIO CONFIGURATION
Space Temp input [nciLogicalInVav, SpcTemp]
Display
UI_1
universal input 1
UI_2
UI_3
UI_4
210
TR71 or TR75 Wall Module
--
none

CONTROL CONFIGURATION

Parameter Group Name
Reheat configuration [nciHeat, Reheat]
63-2730—01
Description
Display
CLG
cooling only
1 rH
1 stage reheat
2 rH
2 stage reheat
3 rH
3 stage reheat
A rH
analog (mod) reheat
Heating Sequence [nciHeat, HeatSeq]
Display
rH
0: reheat only
P rH
1: peripheral then reheat
rH P
2: reheat then peripheral
rP A
3: reheat & peripheral then reheat airflow
PrPH
4: peripheral only
Constant or modulating airflow with reheat [nciHeat,
ReheatControl]
Display
FALS
Constant airflow with reheat
trUE
Airflow modulates with reheat up to the max
reheat airflow