Heating throttling range [nciHeat, TR]
Suggested:
Type
Modulating
5
1 stage
3
2 stage
4
3 stage
7
4 stage
8
2  range  30 F
Heating integral time [nciHeat, IT]
Suggested:
Type
Modulating
2400
1 stage
3100
2 stage
2500
3 stage
1650
4 stage
1200
0  range  5000 sec
TR (F)
IT (sec)
STRYKER VAV ZIO CONFIGURATION
Configure fan type [nciFan, Type]
Display
nOnE
no fan
SErS
Series fan
P tC
Parallel fan temperature control
P AF
Parallel fan airflow threshold
PSPd
Parallel fan speed control
Choose Occupancy sensor opertation [nciOccSensorOp]
Display
CLn
Cleaning crew, when sensor trips during scheduled
unocc, go to standby. During scheduled occ, space
stays in standby unless occ sensor tripped
COnF
Conference room, when sensor trips during
scheduled unocc, stay unocc. During scheduled
occ, space stays in standby unless occ sensor
tripped
tnnt
Tenant, when sensor trips during scheduled unocc,
go to occupied. During scheduled occ, space stays
in standby unless occ sensor tripped