Tenant View More; Contractor View - Parameter Groups - Honeywell Stryker VAV Operating Manual

Zio configuration
Table of Contents

Advertisement

Center SetPoint & Room Temperature (setpoint is adjustable
from Home Screen)
Default Home Screen. Room Temperature & Center SetPoint
(setpoint is adjustable from Home Screen)
Room Temperature (setpoint is NOT adjustable from Home
Screen)
STRYKER VAV ZIO CONFIGURATION

TENANT VIEW MORE

NOTE: To add or remove items from the Tenant View
More sequence use Contractor Mode by holding
the up, down and center buttons for 5 seconds.
During this time the display will show the model,
firmware version and Sylk bus address of the
TR71/75. Select "SetViewMore" to add or remove
items by choosing "YES" or "NO" with the up/
down buttons.
Center Setpoint Temperature
NOTES:
1.
The center setpoint can be disabled using Con-
tractor View: WM_CONFG, CNTR_SP, FALS or
true.
2.
If CNTR_SP = FALS, the set point can be
changed, however the value is ignored.
3.
The range can be controlled by WM_CONFG:
CNTSP_HI, & CNTSP_LO
4.
To remove the CNTR_SP from the View More
screen use Contractor Mode: SetViewMore, SET-
POINT = NO
CONTRACTOR VIEW -
PARAMETER GROUPS
View sensor parameters
3
63-2730—01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents