Programming unit:
■ Easy operation through display with large font and depiction with
good contrast
■ Removable programming unit; can be mounted as option on the wall
with separate accessory
■ Menu prompts through pictograms
■ Operating keys for:
– Navigation
– Confirmation
– Settings/menu
■ Settings:
– Boiler water temperature
– DHW temperature
– Operating program
– Codes
– Actuator tests
– Test mode
■ Displaying:
– Boiler water temperature
– DHW temperature
– Operating data
– Diagnostic details
– Fault messages
Functions
■ Electronic boiler control unit for operation at a constant boiler water
temperature
■ Room temperature-dependent operation requires a Vitotrol 100,
type UTA, UTDB or UTDB-RF (according to EnEV [Germany])
■ Heating system frost protection
■ Pump anti-seizing protection
■ Integral diagnostic system
■ Cylinder temperature controller with priority control
■ Control of solar DHW heating and central heating backup in con-
junction with the solar control module, type SM1
■ Auxiliary function for DHW heating (short-term heating to a higher
temperature)
■ Maintenance display

Specification Vitotronic 100, type HC1B

Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
6 A
Safety category
I
Function
Type 1 B to EN 60730-1
Permissible ambi-
ent temperature
– during operation
0 to +40 °C
Installation in living spaces and boiler rooms
(standard ambient conditions)
VITODENS 200-W
°C
■ External starting and blocking (in conjunction with extension EA1)
■ Connection of the circulation pump for cylinder heating on the main
PCB
Control characteristics
PI characteristics with modulating output.
Setting the heating programs
The heating system frost protection (see frost protection function)
applies to all heating programs.
The following heating programs can be selected:
■ Heating and DHW
■ Only DHW
■ Standby mode
Frost protection function
The frost protection function is active in all heating programs.
The burner is switched ON at a boiler water temperature of 5 ºC and
will be switched OFF again at a boiler water temperature of 20 ºC.
The circulation pump will be switched ON simultaneously with the
burner and switched OFF after a delay.
The DHW cylinder will be heated to approx. 20 ºC.
To protect the system against frost, the circulation pump may be star-
ted at certain intervals (up to 24 times per day) for periods of approx.
10 minutes.
Summer mode
Operating program "w"
The burner starts only when the DHW cylinder needs to be heated up
again.
Boiler water temperature sensor
The boiler water temperature sensor is connected to the control unit
and built into the boiler.
Specification
Sensor type
Permissible ambient temperature
– during operation
– during storage and transport
Cylinder temperature sensor
The standard delivery includes the DHW cylinder connection set.
Specification
Lead length
IP rating
Sensor type
Permissible ambient temperature
– during operation
– during storage and transport
– during storage
and transport
–20 to +65 °C
Electronic tempera-
ture controller set-
ting (heating mode) 82 °C (no change possible)
Electronic high limit
safety cut-out set-
ting
100 °C (no change possible)
DHW temperature
10 to 68 °C
setting range
Viessmann NTC, 10 kΩ at
25 °C
0 to +130 °C
–20 to +70 °C
3.75 m, fully wired
IP 32
Viessmann NTC 10 kΩ at
25 °C
0 to +90 °C
–20 to +70 °C