Fd01 (Inverter Status (Real Time)); Fd00 (Output Frequency (Real Time)) - Toshiba TOSVERT VF-AS1 Series Function Manual

Ethernet/ip option unit
Hide thumbs Also See for TOSVERT VF-AS1 Series:
Table of Contents

Advertisement

3.2.4.9. FD01 (Inverter status (real time))

bit
Function
0
Failure FL
1
Failure
2
ALARM
3
(Undefined)
Motor selection (1 or 2)
4
(THR 2 selection)
5
PI control OFF
Acceleration/
6
deceleration
selection (1 or 2)
7
DC braking
8
Jog run
9
Forward/ reverse run
10
Run/stop
11
Coast stop (ST=OFF)
12
Emergency stop
13
Standby ST=ON
14
Standby
15
Local/ Remote*
Note: The bit described "Undefined" is unstable. Don't use the bit for the judgment.
** This function is reserved in VF-AS1.
3.2.4.10.

FD00 (Output frequency (real time))

The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
- FD22 (Feedback value of PID (real time)) ................................. Unit: 0.01Hz
- FD16 (PG feedback or Estimated speed (real time))................. Unit: 0.01Hz
- FD29 (Input power (real time))................................................... Unit: 0.01kW
- FD30 (Output power (real time) ................................................. Unit: 0.01kW
0
No output
Not tripped
No alarm
-
Motor 1
(THR1)
PI control
permitted
Acceleration/
pattern
deceleration
pattern 1 (AD1)
OFF
OFF
Forward run
Stop
ST=ON
Not emergency
stop status
Start-up process
Start-up process
Remote
- 17 -
1
Output in progress
The statuses include rtry
Tripped
and trip retention status.
Alarm issued
-
Motor 2
THR1: thr
(THR2)
THR2: f173
PI control
prohibited
Acceleration/
AD1: acc, dec
deceleration
AD2: f500, f501
pattern 2 (AD2)
Forced DC
braking
Jog run
Reverse run
Run
ST=OFF
Emergency stop
status
Standby:
completed,
status, not alarm stop status
Standby
(MOFF, LL, forced stop or
forced stop due to a momentary
power failure), ST=ON, and
RUN=ON
Standby: Initialization completed,
not failure stop status, and not
Standby
alarm stop status (MOFF, LL,
forced stop or forced stop due to
a momentary power failure)
Local
E6581581
Note
-
-
-
-
-
-
-
-
-
-
Initialization
not
failure
stop
-