3.2.4.2. FA06 (Command word 1)

bit
Function
Preset Speed
0
operation frequencies 1
Preset Speed operation
1
frequencies 2
Preset Speed operation
2
frequencies 3
Preset Speed operation
3
frequencies 4
Motor selection (1 or 2)
4
(THR 2 selection)
5
PI control
Acceleration/decelerati
on pattern selection (1
6
or 2)
(AD2 selection)
7
DC braking
8
Jog
9
Forward/reverse
10
Run/stop
11
Coast stop command
12
Emergency stop
13
Fault reset
Frequency
14
selection
Command
15
selection
Note: Set 0 to reserved bit.
0
Preset speed operation is disabled
or preset speed operation
frequencies (1-15) are set by
specifying bits for preset speed
operation frequencies 1-4.
(000: Preset speed operation OFF,
001-111: Setting of preset speed
operation frequencies (1-15))
Motor 1
(THR1)
Normal operation
Acceleration/dec
eleration pattern
1 (AD1)
OFF
OFF
Forward run
Stop
Standby
OFF
OFF
priority
OFF
priority
OFF
- 14 -
1
Motor 2
THR1: thr
(THR2)
THR2: f173
PI OFF
Acceleration/dec
AD1: acc, dec
eleration pattern
AD2: f500, f501
2 (AD2)
Forced DC
braking
Jog run
Reverse run
Run
Coast stop
Emergency stop Always enabled, "E" trip
No data is returned from the
Reset
inverter
Enabled regardless of the setting of
Enabled
fmod
Enabled regardless of the setting of
Enabled
cmod
E6581581