Command Data (F831-F838), Monitor Data (F841-F848); How To Use Instance 102/152 And 103/104 - Toshiba TOSVERT VF-AS1 Series Function Manual

Ethernet/ip option unit
Hide thumbs Also See for TOSVERT VF-AS1 Series:
Table of Contents

Advertisement

3.2.4.

Command data (f831-f838), Monitor data (f841-f848)

The outline is indicated about the setting item of parameter f831 - f838 and
f841 - f848 in Instance 102/152 and 103/104 of use. Please refer to a
communication functional description (VF-AS1: E6581315/VF-PS1: E6581413) for
details.

3.2.4.1. How to use Instance 102/152 and 103/104

Instance 102/152 and 103/104 choose a command or the monitor of the driving state by a menu of f831 -
f838 and f841 - f848 and can perform the communication that is cyclic of EtherNet/IP™.
Example 1: Command transmitting by output Instance 102
When it runs by EtherNet/IP™ communication and wants to order you, please choose parameter FA06 (a
communication option command) for command data (f831=1 (FA06)).
For example, please set 0xC400 in FA06 when you want to send the command from an EtherNet/IP™
option and the availability of the frequency order and a driving order. (Please refer to next page)
VF-AS1/PS1
Parameter
1 (FA06)
f831
f832
f833
...
"0xC400" is set as parameter FA06
Example 2: State monitoring by the input instance 152.
When you want to monitor the output current, set "3 (FD03)" to parameter f841.
The value of the parameter
f841 is inputted.
VF-AS1/PS1
Parameter
3 (FD03)
f841
f842
f843
...
The value (ex. 1234) of a parameter FD03
Value
...
...
...
specified as 0 and 1 byte of the input instance 152 with the parameter
FD03
Value
...
...
...
is outputted.
IPE001Z
IPE001Z
- 13 -
E6581581
EtherNet/IP Master
Output Instance102
Byte
Value
0
00
1
C4
2
...
3
...
...
...
EtherNet/IP Master
Input Instance152
Byte
Value
0
34
1
12
2
...
3
...
...
...

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tosvert vf-ps1 seriesTosvert ipe001z