Download Print this page

YASKAWA DI-101 Installation Manual page 17

Ac drive option, 120 vac digital input

Advertisement

6.
Prepare the external 120 Vac control circuit wires (customer supplied) for terminals
S1 to S8 and X2 on the DI-101 option as shown in
Figure 7
Preparing wire ends:
Strip wire insulation about 5.5 mm
and lightly twist the end with fingers,
keeping the ends from fraying.
7.
Connect the customer wiring to the DI-101 option terminal block. Refer to
for a wiring diagram example showing customer interface circuitry.
Refer to Wire Gauges, Tightening Torques, and Crimp Terminals on page 20
confirm that the proper tightening torque is applied to each terminal. Take particular
precaution to ensure each wire is properly connected and wire insulation is not
accidentally pinched into electrical terminals.
WARNING! Fire Hazard. Tighten terminal screws to the specified tightening torque. Loose electrical
connections could result in death or serious injury by fire due to overheating. Tightening screws beyond the
specified tightening torque may cause erroneous operation, damage the terminal block, or cause a fire.
YASKAWA TOEP YEAOPT 07 A1000 Option DI-101 120 Vac Interface Installation Manual
Screwdriver blade size
about 5.5 mm (7/32")
When not using
crimped insulated
sleeves
Loosen the screws and
insert the wire into the
opening on each terminal.
120 Vac control circuit wires
Figure 7 Preparing Cable Wiring
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
Customer-supplied
(do not solder ends)
5 Installation Procedure
Figure
7.
S1S2 S3 S4
S5
S6
DI-101 Option Terminal Block
S7
S8
X2
X2
Figure 8
to
17