Siemens Desigo RXB Technical Manual page 439

Technical manual
Table of Contents

Advertisement

Four-pipe fan coil with outside air damper
Plant diagram
N1
Room controller.
R1
Room unit with temp.
sensor.
B1
Return air sensor.
B2
Outside air temperature
sensor via KNX bus.
D1
Window switch.
D2
Presence detector.
D3
Safety thermostat, outside
air.
Q1
Fan (1... 3-speed).
YH
Heating valve.
YC
Cooling valve.
YM
Outside air damper.
Operating diagrams
Y
Output signal.
TR
Room temperature.
TO
Outside air temperature.
SpH
Effective heating setpoint.
SpC
Effective cooling setpoint.
SpEcm Economizer setpoint.
SpFr
Risk of frost limit
H
Heating sequence.
C
Cooling sequence.
YH
Heating valve.
YC
Cooling valve.
YM
Outside air damper.
Q14
Fan speed 1.
Q24
Fan speed 2.
Q34
Fan speed 3.
Siemens
Building Technologies
Heating and cooling with LTHW and cooling with CHW.
Modulating control of heating and cooling valve.
Outside air damper for outside air supply.
Outside air temperature sensor via KNX bus.
Automatic or manual fan control.
YC
YH
YM
D3
M
N1
K N X
R
Y [%]
H
100
YH
0
SpH
SpC
Y
H
Q34
Q24
Q14
SpH
SpC
RXB application library (KNX)
FNC12 – Four-pipe fan coil with outside air damper
Q1
T
B1
T
R1
Y [%]
C
100
YC
min
0
TR [°C]
C
TR [°C]
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
FNC12
K NX
B2
D1
D2
YM
SpFr
SpC
SpEcm
CM110672en_03
R
TO [°C]
37/52
30.11.2007