Sensor correction
Parameter
Measured value correction
Note
Setpoint shift range
Parameter
Setpoint offset range
Local Comfort mode
(LTE mode only)
Parameter
Local Comfort mode
Room unit
Parameter
Room unit
Display heating and
cooling symbols
(ETS only)
Parameter
Show heating/cooling symbols
Select temperature unit
Parameter
Temperature unit
Siemens
Building Technologies
The measured value of the integrated temperature sensor can be corrected to
compensate e.g. wall installation issues.
Basic setting
0 K
This correction is also valid for a sensor that is connected to the analog input B1 (but
not for a bus sensor).
The maximum setpoint shift range is as follows (see also page 72).
Basic setting
± 3 K
A central station together with communication object Enable comfort (see page 57)
can prevent the room operating mode from being more than Economy (to save energy).
Enable Comfort , however, can be ignored in the room controller via the following
parameter:
Description
Change from Economy to Precomfort or Comfort mode.
Enabled (basic setting)
Precomfort or Comfort can be disabled via the Enable
Comfort input.
Disabled (ignore Enable Comfort input). Precomfort or
Comfort CANNOT be disabled via the Enable Comfort
input.
You can choose whether or not the room unit has an LCD display. If yes, the following
parameters can also be set.
Beim HandyTool ist fix "Mit LCD" eingestellt.
Description
Without LCD / with LCD
The display of the heating and cooling symbols can be enabled or disabled. Note that
this applies only to room units with an LCD display.
Symbols:
Cooling sequence active
Heating sequence active
Description
Displays heating and cooling symbols.
The room temperature can be displayed either in Celsius (°C) or Fahrenheit (°F). Note
that this applies only to room units with an LCD display.
Value
(Only room units with LCD).
Celsius (°C) (basic setting).
Fahrenheit (°F)
RXB (KNX) Applications library
Room unit
Range
– 3 ... 3 K
Range
± 0 ... 10 K
CLC and RAD description of functions for CC-02 CM110384en_03
Resolution
HandyTool
0,1 K
*101
Resolution
HandyTool
1 K
*103
HandyTool
*105
1
0
Basic setting
Without LCD
Basic setting
Enabled
HandyTool
*108
1
0
115/140