Siemens Desigo RXB Technical Manual page 324

Technical manual
Table of Contents

Advertisement

ETS3 Professional
ACS Service
HandyTool
Parameters 4-pipe
Running time heating valve
Running time cooling valve
Offset heating valve
Offset cooling valve
88/166
Siemens
Building Technologies
Select Sequences . After selection of third-party devices, a new window opens in which
the heating and cooling runtimes can be set.
Select the actuator runtime from Sequences :
See Parameters in the last column of the table below
Motorized and electromechanic valves.
Basic setting
150 s
150 s
0 s
0 s
RXB (KNX) application library
Control sequences
Range
0 ... 360 s
0 ... 360 s
0 ... 360 s
0 ... 360 s
FNC Description of functions for FC-10, FC-11, FC-12
Resolution
HandyTool
1 s
*061
1 s
*062
1 s
*071
1 s
*072
CM110385en_05
28 Feb 2009